Disable a Zone – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>1.Zone
If a zone is disabled the system will not display any  re or fault events for
devices located in that zone. This includes any call point activations. Select
the zone number to be disabled and press the key. Select the time-out
period followed by the key. All access levels can disable a zone for a pe-
riod of 1 to 96 hours. A commissioning user can disable a zone inde nitely
by selecting a time of ‘00’ hours. Press Enter to save the change. ‘Zone
XXX disabled will be displayed on screen and the LED marked ‘Disable-
ments’ will now be illuminated on the panel. After the time out period has
elapsed, the isolated zone(s) will automatically be re-enabled.
Disable a Device – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>2.Device
If a device is disabled the system will not display any  re or fault events for
that device. Using the or keys select the device number to be disabled
and press the key. Select the timeout period followed by the key.
All access levels can disable a zone for a period of 1 to 96 hours. A
commissioning user can disable a zone inde nitely by selecting a time
of ‘00’ hours. Press Enter to save the change. ‘Device XXX disabled’ will be
displayed on screen and the LED marked ‘Disablements’ will now be
illuminated on the panel. After the timeout period has elapsed, the
isolated device(s) will automatically be re-enabled. Press Cancel to exit
or Enter to disable more devices. If all devices in a zone are disabled, the
zone is also disabled. If a sounder detector is disabled, only the detector
component ceases to function. The device will still sound in an alarm. If a
square sounder is disabled, only the reporting of faults from the device is
disabled – the sounder will still sound in an alarm.
Disable Panel Inputs – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>3.Panel Input
The two monitored inputs can be disabled for a period of time speci ed by the user, dependent on their access
level. All access levels can disable an input for a period of 1 to 96 hours. A commissioning user can disable an input
inde nitely by selecting a time of ‘00’ hours. Press Enter to save the change ‘Input XXX disabled’ will be displayed
on screen and the LED marked ‘Disablements’ will now be illuminated on the panel. The system will ignore any
re or fault event from that input within that time. After the timeout period has elapsed any disabled inputs will
automatically be enabled again.
7.0 - DISABLE/ENABLE