6.34 - Reprogram Device – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>5.Reprogram Device
Some settings such as operating mode, sensitivity, volume, device alarm veri cation period and sounder area are
stored on the device rather than the control panel. In order to change these settings the device will need to be put
into programming mode. First remove the device from its base or back plate.
1. If a smoke or heat detector is being reprogrammed; hold both the reset button and the unit removal
button down while you place the jumper link to the ON position.
2. If a sounder, beacon, callpoint, transmitter or I/O unit is being reprogrammed; hold down the unit removal
button while holding a magnet over the reed switch and place the jumper link to the ON position. Some
newer callpoints are equipped with a ‘log on button. Hold this while placing the jumper link to the ON
position.
Continue to hold the button(s) until a con rmation of 3 beeps from the device is heard, then release the buttons
and remove any magnet. The LED on the device will now  ash green. Press Enter to scan for the device. Once the
device has been found, the device type will be displayed on the screen. The LED on the device will stay lit until the
device has been successfully reprogrammed. The device number for the new unit should be selected using the
cursor keys. When correct press Enter. You will now be prompted to choose from using either the device default
settings set by the control panel or to manually set up the cause and e ects. All options are entered using the cur-
sor keys. Once you have chosen the options, press Enter to program.
6.35 - System Test
Test Devices – commissioning users
1.Main Menu>>1.Setup>>6.System Test>>1.Test Devices
This can be used to activate certain functions on a speci c device. These can be used to assist in locating a device,
or as a test of functionality. The available options are:
Activate A sounder will sound for 3 short tones, a beacon will  ash 3 times.
Silence The device will silence (if it is currently sounding).
Reset The device will reset.
LED On The led on the device will illuminate solid green.
Buzzer On The buzzer on the device will sound.
Panel – Panel Test – commissioning users
1.Main Menu>>1.Setup>>6.System Test>>2.Panel – Panel Test
The panel to panel test allows the user to select two panels on the system and view the signal strengths between
them.
Pager Test Message – commissioning users
1.Main Menu>>1.Setup>>6.System Test>>3.Pager Test Message
This tool allows the user to send a test alert message to any pagers set up on the system.