Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 3
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
Maximum number of zones F/EDA-Z5008 8
F/EDA-Z5020 20
F/EDA-Z5100 100
Maximum Number of Devices 240
Maximum Number of Repeater Panels 7
Maximum Total Number of Antennas 15
Dimensions (not including antenna) 275(W) x 220(H) x 85mm(D)
Weight (not including battery) 4kg
Operational Temperature -5C to +40C
IP Rating IP30
Alarm Indicators Twin ashing red LEDs
Red individual zone LEDs
Fire message on LCD with 40 characters of text
Fault Indicators Amber LEDs and LCD providing details and location of fault
with 40 characters of location text
Event Log Memory 1000 events maximum
Mains Supply 230V 50Hz 0.3A max
Mains Fuse 1 x 250V 3.15A
Battery 1 x 12V 7.0Ah sealed lead acid giving 72 hour standby
Battery Fuse 1 x 250V 3.15A
Relay Fuses 4 x 250V 500mA
RS485 Fuse 1 x 250V 500mA
Inputs 2 x wired monitored circuit. 4k7 (±5%) end of line (EOL) resistor
monitored for open and short circuit, 470 (±5%) alarm load
Relays 4 x programmable
Relay Types Fire Relay Clean Contact
Fault Relay Clean Contact
Sounder Circuit 10-18V, 500mA, 4k7 (±5%) EOL
Fault Relay Safe Clean Contact
Fire Routing Relay 10-18V, 500mA, 4k7 (±5%) EOL
Operating Frequency 8 68MHz (868.025 to 868.575MHz)
Modulation 2-GFSK
Output Power (ERP) <25mW (<14dBm)
Channel Spacing 50KHz
Error Checking CRC
Error Correction Hamming
Number Of Channels Available 12
Compatible With Zerio Plus products only
Protocol ZPNet V1.00
SPECIFICATION