Instruction manual

INSTRUCTION MANUAL - Issue 1 - 07/2014 | 29
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
6.30 - Remove a Device – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>3.Remove Device>>1.Remove
One Device
If a device is not required on the system it must be deleted to prevent it
causing a verify fault once powered down. From the Device Setup menu
select ‘3 – Remove Device then select ‘1-Remove One Device. Using the
cursor keys select the device number and press . Select if you would
like to keep the location text of the device and press . Press Enter to
con rm the removal. All programming will be deleted.
6.31 - Remove all Devices – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>3.Remove Device>>2.Remove All
Devices
It would be unusual to remove all devices from a system unless it was
being completely re-installed or decommissioned. From the Device Setup menu select ‘3-Remove Devices’ then
select ‘2-Remove All Devices’. Press Enter to con rm removal of all the devices from the system. All programming
and text will be deleted. The system number and RF channel will remain the same.
6.32 - Edit Device Options – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>4.Edit Device>>1.Device Options
Use this menu to change the zone number or any cause and e ects for a device. Some options can only be
changed by reprogramming the device; see 6.34 – Reprogram Device. Device options are listed below. Once the
device options have been edited, press until ‘press Enter to save’ is displayed.
Zone The zone the device is located in.
Delay1 The rst delay before the sounders operate.
Tone1 The tone that the sounders should operate after delay1.
Area1 The area that should sound after delay1 (sounders will have to be programmed to this area
to operate); see 6.34 – Reprogram Device.
Relay1 Hardwired relay operation inside the control panel after delay1.
Delay2 The second delay before the sounders operate.
Tone2 The tone that the sounders should operate after delay2.
Area2 The area that should sound after delay2.
Relay2 Hardwired relay operation inside the control panel after delay1.
IP1 Device Activates the devices secondary input.
HMO Device Speci es if the device is to be used in an HMO dwelling.
6.33 - Device Text – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>4.Edit Device>>2.Device Text
Each device can have location text programmed into the control panel using either a USB keyboard or via the
control panel. The text can be programmed when the device is being added or can be entered or amended at
a later date. If using a keyboard connect it to the panel before entering the main menu. From the Device Setup
menu select ‘4-Edit Device’, then select ‘2-Device Text. If entering text via the panel use the key to display the
characters. Browse the characters using the keys; select the character using the . Menu key is SPACE and
Function is a BACKSPACE. Once complete press to hide the characters and press . Con rm the text is correct
and press Enter to save. If more text is to be amended press Enter. To return to the menu press Cancel.