Instruction manual

INSTRUCTION MANUAL - Issue 1 - 07/2014 | 27
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
6.28 - Device Information
View Device Info – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>1.View Device Info
This menu allows the user to select a device and see all available
information for it, including what zone the device is in, the device numbers
of any inputs it has, any cause and e ects con gured for it and the text
location (if programmed). Press and to scroll through the pages.
Dump Device Info to USB – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>2.Dump Device
Info to USB
The panel can dump the device information on to a USB memory stick for
viewing on PC. Users can select to copy either ‘1-Basic Info or ‘2-Advanced
Info. Basic information includes the device number, type, zone and text
location. Advanced information also includes cause and e ect settings for each device.
Device Version – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>3.Device Version
Select a device and press Enter to poll that device. This will display the version number of the  rmware on the
selected device.
Device RSSI – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>4.Device RSSI
Select a device and press Enter to poll that device. This will display the received signal strength indicator informa-
tion for a particular device. The RSSI scale goes from -20 to +20, with +20 being the best. If signal strengths for all
devices are required, it will be quicker to view the strengths in the verify table; see 10.0 – Verify Table.
Device Battery Level – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>5.Device Batt Level
Select a device and press Enter to poll that device. This will display the voltage for each battery cell in the device.
Each EDA-Q690 battery pack has 2 cells.
Device Head Level – service and commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>1.Device Info>>6.Device Head Level
Select a device and press Enter to poll that device. This will display the level of contamination in the sensor head of
the device.