Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 23
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
6.15 - Input Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>1.Input Options
This menu allows the user to set options for the two monitored inputs. The default settings have been type
approved. Selecting some of the available options may result in a system which is not EN54-2 approved. If unsure,
contact us for advice.
Select Input Choose from input 1 or 2.
IP Type Disabled, Latching IP, Non-latching IP or keyswitch. Latching IP is type approved.
Zone Zone number of the hardware connected to the input.
Delay1 First delay before the sounders operate.
Tone1 Tone that the sounders sound after delay1. The SWEPT tone has been type approved.
Area1 The area that should sound after delay1 (sounders will have to be programmed to this area to
operate); see 6.34 – Reprogram Device.
Relay1 Hardwired relay operation in the panel after delay1. Types 0 and 3 are type approved.
Delay2 Second delay before the sounders operate.
Tone2 Tone that the sounders sound after delay2. The SWEPT tone has been type approved.
Area2 The area that should sound after delay2.
Relay2 Hardwired relay operation in the panel after delay2. Types 0 and 3 are type approved.
These are the available relay types for the ‘Input Options’ menu.
0. Relays O
1. Sounders Pulse 1
2. Sounders Pulse 2
3. Fire & Sounders On
4. Fire On
5. Sounders On
6. Fire & Sounders Pulse 1
7. Fire & Sounders Pulse 2
8. User Relay A
9. User Relay B
10. User Relay C
11. User Relay D
6.16 - Input Text – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>2.Input Text
This menu allows the user to assign text names to each of the inputs. Select the input, then enter text using the
panel or by connecting a standard USB keyboard. Press Enter to save. Multiple devices connected to an input (i.e.
hardwired detectors) cannot be individually assigned text names.
6.17 - Keyswitch Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>3.Keyswitch Options
This menu allows the user to set up a keyswitch on the inputs.