Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 21
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
6.9 - System Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>2.System Options
This menu allows the user to change overall system settings.
Alarm Verify Time (seconds) that a device has to be in alarm to generate an alarm condition on the
panel. 2 seconds has been type approved.
Antenna Type Specify if the main panel is using a Stub, Dipole or Yagi antenna. STUB has been type ap
proved.
Code Protect Whether an access code is needed to silence or reset an alarm or fault. Default is set to ON.
ON has been type approved.
Sil Alm Delay Length of time (seconds) the ‘Silencing – Please Wait’ screen is displayed. 5 sec has been
type approved.
Res Alarm Delay Delay between pressing the reset button and the system resetting an alarm condition. 5
sec has been type approved.
Res Flt Delay Delay between pressing the reset button and the system resetting a fault condition. 5 sec
has been type approved.
Auto Resound When set to By Zone; if an alarm condition has been silenced and another device goes into
alarm, the sounders will only start sounding again if the device is in a di erent zone. When
set to By Device; if an alarm condition has been silenced, any other device which goes into
alarm will cause the sounders to start sounding again.
6.10 - Fault Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>3.Fault Options
This menu allows the user to enable or disable certain types of faults, and to change the levels or time periods re-
quired to produce a fault condition. The default settings have been type approved. Selecting some of the available
options may result in a system which is not EN54-2 approved. If unsure, contact us for advice.
Verify Time Time without communication from a particular device before the system generates a verify
fault. The default is 390 seconds. Verify times of 390 seconds or less have been type ap
proved.
Show Batt Low Enable or disable faults for low battery alerts from devices.
Batt Low T/out If disabled, the time period until faults for low battery automatically re-enable.
Show Int Fail Enable or disable faults for internal failures from devices.
Int Fail T/out If disabled, the time period until faults for internal failures automatically re- enable.
Interference The level of interference required for the panel to generate an interference warning. This is
set to o by default.
Interference Period The minimum length of the interference required for the panel to generate an interference
warning.
Head Dirty The percentage of contamination in the head required to generate a ‘Head Dirty’ fault.
Pre Alarm The percentage of contamination in the head required to generate a pre-alarm condition.
Show Batt Warning Enable or disable warning messages for low panel battery.