Instruction manual

INSTRUCTION MANUAL - Issue 1 - 07/2014 | 20
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
6.8 - User Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>1.User Options
Detailed below are the other options that can be changed related to the panel. The default settings have been
type approved. Selecting some of the available options may result in a system which is not EN54-2 approved. If
unsure, contact us for advice.
Panel Zone The zone the panel is located in.
Func Key Set the function key as disabled, evacuate, alert or delay toggle.
Func Tone The tone to be sounded if the function key is pressed and has been programmed as either
evacuate or alert. The SWEPT tone has been type approved.
Func Relay The relay to be operated if the function key is pressed and has been programmed as either
evacuate or alert. The FIRE & SOUNDERS ON setting has been type approved.
Double Knock Whether double knock is enabled. See 14.0 – Delays.
Double Knock Tone The tone to be sounded after second device activates. The SWEPT tone has been type ap
proved.
Double Knock Relay The relay to be operated after second device activates. The FIRE & SOUNDERS ON setting
has been type approved.
Double Knock Zone Whether a second device in the same zone or any second device operates the double
knock.
Relay 1 Type Choose relay type 0 to 5. Default setting is 5. FIRE ROUTING has been type approved.
Relay 1 Reset Whether Relay 1 is cleared upon pressing silence or upon pressing reset.
Relay 2 Type Choose relay type 0 to 5. Default setting is 4. FAULT RELAY SAFE has been type approved.
Relay 2 Reset Whether Relay 2 is cleared upon pressing silence or upon pressing reset.
Relay 3 Type Choose relay type 0 to 5. Default setting is 3. SOUNDER has been type approved.
Relay 3 Reset Whether Relay 3 is cleared upon pressing silence or upon pressing reset.
Relay 4 Type Choose relay type 0 to 5. Default setting is 3. SOUNDER has been type approved.
Relay 4 Reset Whether Relay 4 is cleared upon pressing silence or upon pressing reset.
The relay types are listed below:
Type 0 Disabled
Type 1 Fire Relay
Type 2 Fault Relay
Type 3 Sounder circuit
Type 4 Fault Relay Safe
Type 5 Fire Routing Relay
The relay types are con gured not only in the panel software but also by physically placing jumper links on
the panel PCB. Refer to page 11 for relay link positions and fuse requirements.
To ensure EN54-2 compliance refer to section 1.0 of this manual for default settings. The panel was type approved
in this con guration.