User manual
EDA-Z5008, Z5020 & Z5100 – User Manual ZPControlUserMan_r100
_____________________________________________________________________________________________________
12
Disable Panel Inputs – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>3.Panel Input
The two monitored inputs can each be disabled for a period of time specified by the user, dependent
on their access level. All access levels can disable an input for a period of 1 to 96 hours. A
commissioning user can disable an input indefinitely by selecting a time of ‘00’ hours. Press Enter to
save the change ‘Input XXX disabled’ will be displayed on screen and the LED marked ‘Disablements’
will now be illuminated on the panel. The system will ignore any fire or fault event from that input
within that time. After the timeout period has elapsed any disabled inputs will automatically be
enabled again.
Disable Sounders – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>4.Sounders
The sounders can be disabled for a period of time specified by the user, dependent on their access
level. All access levels can disable a sounder for a period of 1 to 96 hours. A commissioning user can
disable a sounder indefinitely by selecting a time of ‘00’ hours. The sounders will ignore any fire event
from the panel within that time. Both the ‘Disablements’ LED and the ‘Sounder Flt/Disable’ LED will be
illuminated. After the timeout period has elapsed any disabled sounders will automatically be enabled
again. When sounders are disabled, any hard wired sounder circuits will not display short circuit and
open circuit faults.
Disable Fire Routing – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>5.Fire Routing
The fire routing relay can be disabled for a period of time specified by the user, dependent on their
access level. All access levels can disable the relay for a period of 1 to 96 hours. A commissioning user
can disable the relay indefinitely by selecting a time of ‘00’ hours. The relay will ignore any fire event
from the system within that time. The ‘Disablements’ LED and the ‘Routing Flt/Disable’ LED will be
illuminated. After the timeout period has elapsed, the relay (if still disabled) will automatically be
enabled again. When Fire Routing is disabled, open circuit and short circuit faults will not be reported.
Disable Fault Relay – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>6.Fault Relay
The fault relay can be disabled for a period of time specified by the user, dependent on their access
level. All access levels can disable the relay for a period of 1 to 96 hours. A commissioning user can
disable the relay indefinitely by selecting a time of ‘00’ hours. The relay will ignore any fault event from
the system within that time. After the timeout period has elapsed, the relay (if still disabled) will
automatically be enabled again. To comply with EN54, the fault relay should not be disabled.