User manual

EDA-Z5008, Z5020 & Z5100 User Manual ZPControlUserMan_r100
_____________________________________________________________________________________________________
11
4.0 - Setup Menu
4.1 - Changing the system Time and Date all access levels
1.Main Menu>>1.Setup>>1.Time & Date
To change the time and date settings use the and keys to
navigate to the value, and the or keys to select the desired
value. Press Enter to accept or Cancel to exit. The Zerio Plus panel
automatically adjusts the clock for daylight savings. Should
complete power be lost the panel will revert the time back to the
default of 01/01/2013 12:00:00
5.0 - Disable/Enable
Disable a Zone all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>1.Zone
If a zone is disabled the system will not display any fire or fault
events for devices located in that zone. This includes any call point
activations. Select the zone number to be disabled and press the
key. Select the timeout period followed by the key. All access
levels can disable a zone for a period of 1 to 96 hours. A
commissioning user can disable a zone indefinitely by selecting a
time of ‘00’ hours. Press Enter to save the change. ‘Zone XXX
disabled’ will be displayed on screen and the LED marked
‘Disablements’ will now be illuminated on the panel. After the
timeout period has elapsed, the isolated zone(s) will automatically
be re-enabled.
Disable a Device all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>2.Device
If a device is disabled the system will not display any fire or fault
events for that device. Using the or keys select the device
number to be disabled and press the key. Select the timeout
period followed by the key. All access levels can disable a zone
for a period of 1 to 96 hours. A commissioning user can disable a
zone indefinitely by selecting a time of ‘00’ hours. Press Enter to
save the change. ‘Device XXX disabled’ will be displayed on screen
and the LED marked ‘Disablements’ will now be illuminated on the
panel. After the timeout period has elapsed, the isolated device(s)
will automatically be re-enabled. Press Cancel to exit or Enter to
disable more devices. If all devices in a zone are disabled, the zone
is also disabled. If a sounder detector is disabled, only the detector component ceases to function. The
device will still sound in an alarm. If a square sounder is disabled, only the reporting of faults from the
device is disabled the sounder will still sound in an alarm.
Select Zone 001↕
Use ← → keys
Press ENTER to
Disable Zone 001
Time: 12:39:00
Date: 01-01-2013
ENTER to save
Select Device 001↕
SMOKE DET
Use ← → keys
Press ENTER to
Disable Device 001