Specifications

Engineering Notes
Zephyr Fans
PENNBARRY
18
The following section includes engineering and technical
data, guidelines and system explanations related to air mov-
ing and control devices. Fan laws and system descriptions
are consistent with industry standards, definitions and
accepted practices. They are provided to assist system
designers in sizing, selecting and defining their air moving
and control systems as well as explaining variables inherent
in system design.
Flow And Static Pressure
For any change in static pressure (SP), a squared relationship
is applied to the flow ratio. This is expressed by the formula:
P
2
=
CFM
2
2
P
1
CFM
1
Where P
1
is the original static pressure,
P
2
is the desired static pressure,
CFM
1
is the original flow rate in cu. ft. per minute, and
CFM
2
is the desired flow rate in cu. ft. per minute.
This formula is based upon performance of a fan at one point
on a system. This data can be used to calculate a fan per-
formance curve indicative of all five points from 0" SP (max-
imum flow) to maximum SP (0 flow).
CFM
2
=
RPM
2
P
2
=
CFM
22
HP
2
=
CFM
23
CFM
1
RPM
1
P
1
CFM
1
HP
1
CFM
1
CFM
2
=
RPM
2
P
2
=
RPM
22
HP
2
=
RPM
23
CFM
1
RPM
1
P
1
RPM
1
HP
1
RPM
1
NOTE: Direct drive fans can change speed only through the use of a speed
controller and cannot increase speed beyond catalog maximum. Fans must
operate on single phase in order to change speed.
Air Systems
An air system may consist simply of fan with ducting con-
nected to either the inlet or discharge or to both. A more com-
plicated system may include a fan, ductwork, air control
dampers, cooling coils, heating coils, filters, diffusers, noise
attenuators, turning vanes, etc. The fan is the component in
the system which provides energy to the airstream to over-
come the resistance to flow of the other components.
Component Losses
Every system has a combined resistance to flow which is
usually different from every other system and is dependent
upon the individual components in the system.
The determination of the “pressure loss” or “resistance to
flow”, for the individual components can be obtained from the
component manufacturers. The determination of pressure
losses for ductwork and branch piping design is well docu-
mented in standard handbooks such as the ASHRAE
Handbook of Fundamentals and SMACNA Duct Design
Manual.
The System Curve
At a fixed volume flow rate (CFM) through a given air system
a corresponding pressure loss, or resistance to this flow, will
exist. If the flow rate is changed, the resulting pressure loss,
or resistance to flow, will also change. The relationship gov-
erning this change for most systems is:
PRESSURE
C
/ PRESSURE = (Q
C
/ Q)
2
Q = CFM
C
= change
Interaction Of System And Fan Performance Curve
If the system characteristic curve, composed of the resis-
tance to flow of the system and the appropriate System
Effect Factors have been accurately determined, then the fan
selected will develop the equivalent and necessary pressure
to meet the system requirements; i.e. the fan will deliver the
designated flow rate when installed in the system.
The point of intersection of the system curve and the fan per-
formance curve determines the actual flow volume. If the
system resistance has been accurately determined and the
fan properly selected, their performance curves will intersect
at the design flow rate. Refer to Figure 1. The normalized
Duct System A from Figure 1 has been plotted with a nor-
malized fan performance curve.
The volume flow
rate through the
system in a given
installation may be
varied by changing
the system resis-
tance. This is usual-
ly accomplished by
using fan dampers,
duct dampers, mix-
ing boxes, terminal
units, etc. Figure 1 shows the volume flow rate may be var-
ied from 100% design Q (Point 1, Duct System A), to approx-
imately 80% of the design q by increasing the resistance to
flow, thus changing the system curve characteristics to Duct
System B. This results in fan operation at Point 2 (the inter-
section of the fan curve and the new Duct System B).
Similarly, the volume flow rate can be increased to approxi-
mately 120% of the design Q by decreasing the resistance to
flow, thus changing the system curve characteristic to Duct
System C. This results in fan operation at Point 3 (the inter-
section of the fan curve and the new Duct System C).
()
()
()
()
()
Figure 1