Bulletin Z05 ZEPHYR Model: Z Ceiling Fan
Zephyr Fans Introduction Table of Contents CERTIFIED RATINGS Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Zephyr Fans PennBarry certifies that the Zephyr models shown on pages 4, 5, 13, 14 and 16 are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
Zephyrette & Zephyr Jr. Zephyr Low Profile Fans Features: • Quiet operation – low sone level, non-overloading low power consumption design • Lek-Trol™- variable speed controller can be built into fan housing for precise system balancing and energy conservation • Thermal overload protection integral with motor • Rustless, durable housing of galvanized steel • UL approved Performance and Dimensional Data Model Number Max Watts Motor 60Hz AC Motor RPM Shipping Weight (lbs.
Transfan Room-to-Room Fan Zephyr Transfan Features: Wood or coal burning stoves, gas or oil fired space heaters and fireplaces do an excellent job of economically heating the surrounding space. The PennBarry Transfan is now available to move that heated air through partitions or ceilings to other rooms in your home or office. The Transfan spreads the value of your stove or heater. It’s easy to install, quiet and economical, and effectively moves heated air to remote rooms.
Z1 Compact Economical Fan Features: • 56 CFM, 3.4 Sones @ 0.
ZL1 & ZL2 Ceiling Fans with Light Features: • 62 CFM, 1.9 Sones @ 0.0" Ps – Model ZL1 • 97 CFM, 4.0 Sones @ 0.
Features & Benefits Zephyr Fans Zephyr ceiling and inline fans are designed and constructed to create a quiet and reliable product. Each unit is fully assembled and tested prior to shipment. Extensive combinations of wheel sizes and speeds enable the Zephyr to cover a wide range of CFM. High Static Pressures Complete Range Of Performance EasyTap Speed Selection PennBarry provides the most ceiling fan options of any manufacturer.
Features & Benefits Zephyr Conversion Field Conversion The Zephyr cabinet is designed for quick transition from right angle discharge to top discharge or into an inline configuration. Simply remove two (or four depending upon model) sheet metal screws, switch positions of the access panel and top panel, re-attach screws, and a right angle discharge becomes a top discharge fan. There is no need to remove the power pack. The blower remains oriented in one position while the panels change places.
Features & Benefits Zephyr Installation Hanger Support Rods to Building Structure (By Others) Outlet Duct (By Others) Hanger Support Rods to Building Structure (By Others) Zephyr Housing Outlet Duct (By Others) Adjustable Mounting Flanges Zephyr Housing Zephyr Grille Zephyr Grille ‘TD’ (Top Discharge) Ceiling (By Others) ‘RA’ (Right Angle) Adjustable Mounting Flanges Ceiling (By Others) Zephyr Typical Installation Arrangements STANDARD WITH GRILLE Duct (By Others) Duct (By Others) Housing A
Accessories Zephyr Fans Accessories Matrix Model Flat WCF06 WCF06 WCF06 WCF08 WCF08 WCF08 WCF10 WCF10 WCF12 WCF12 WCF14 WCF14 WCF20 WCF20 Z3H Z5H Z6S/H Z8S/H Z81S Z10S/H Z101S Z102S Z12S Z121S Z102H Z12H Z14 Z15 Roof Caps Curb Mnt.
Accessories Zephyr Fans Roof Caps Ceiling Radiation Damper These spun aluminum, rustproof, seamless vents provide a discharge cap for flat roof mounting. Unobtrusive and furnished with integral bird screen, they are designed for simple, safe flashing directly to the roof. Mounting flanges are also available turned down as cap flashing when installation on roof curbs is desired. See the PennBarry Weathercap Bulletin for more information. For Use With Model LDIA. C H WCC F ADIA. ESQ.
Accessories Zephyr Fans 277 Volt Transformer Vibration Hanger To meet local requirements voltage transformers are available for all Zephyrs. Hanger vibration eliminators feature rubber-in-shear type and are available for use with all units. 1 2" 2 /4" 13/32" HOLE DIAMETER Z3-Z12 3" Pilot Light This amber colored light easily snaps into any opening in the Zephyr grille. The light will indicate when the fan is in operation and is ideal when fan is not interlocked with lights.
Dimensional Data Zephyr Fans RA/TD Zephyrs TDA/TDA-RA Zephyrs Housing Model Z3,5,6 Z8,81 Z10 Z12, 101, 102, 121 A B C D 12 1/2 9 1/8 16 9 1/8 13 7/8 11 3/8 17 3/8 11 3/8 18 14 1/8 21 1/2 14 1/8 24 14 1/8 27 1/2 14 1/8 Outlet Duct E 1 1/4 1 7/8 3 5/8 1 1 E 1 1/4 4 6 3/8 F 5 3/8 5 1/4 8 G 10 8 8 H 3 1/4 6 6 1 8 22 6 Grill TDA Panel J K L 3/4 11 13 3/4 3/4 13 1/4 14 7/8 3/4 15 1/2 19 3/8 X 10 10 14 Y 6 8 10 Z 1 5/8 1 9/16 2 3/4 15 1/2 20 10 2 25 Z3, Z5, Z6 EI E A G J H D ALL DIME
Performance Data - RA/TD Zephyrs Ceiling Mounted Models with Grills • Adjustable Air Flow • Low Sound Level • Decorator Deluxe Grille is Standard • Economical – Excellent Value • Easy to Install and Maintain 4 Zephyr Model No. MAX. WATT Amps RPM 1 Z3H 39 0.5 1550 Z5H 79 1 1550 Z 6S 5 47 0.6 1 05 0 5 108 1.4 1550 6 77 1 1050 Z81S 77 0.9 1050 130 1.6 1550 7 243 2.5 1050 Z101S 153 1.6 1050 Z10H7 390 3.6 1550 Z102S 269 4.5 1050 Z12S 260 2.
TDA/TDA-RA - Performance Data Zephyr Inline Fans • Extensive Capacity Range • Ultra Quiet Operation • Quality Construction Throughout • Adjustable Air Flow Zephyr 4 Model 14 MAX. WATT Amps RPM 1 Z3H (TDA) 42 0.5 1550 Z5H (TDA) Z6S (TDA)5 Z6H (TDA)5 Z8S (TDA)6 Z81S (TDA) Z8H (TDA)6 Z10S (TDA)7 Z101S (TDA) Z10H (TDA)7 Z102S (TDA) 83 1 1550 46 0.6 1050 108 1.4 1550 75 1 1050 84 0.9 1050 132 1.6 1550 234 2.5 1050 152 1.6 1050 372 3.6 1550 273 4.
Performance Data Large Capacity Zephyr Fans • Quiet Design with Insulated Housing • Performance Range to 3290 CFM • Versatile Discharge Directions • Install Easily in Confined Spaces • Optional Grille Available • Easy Access Panel Model No. Z14 115/1/60 1/2 HP Z15 230/1/60 1 HP RPM Inlet Area Outlet Area Wheel Size Circum. Dia. 1150 0.5 1550 8" 2.09' 1060 1 1550 8" 2.09' 980 0.6 1050 8" 2.09' 880 1.4 1550 8" 2.09' 1030 0.9 1050 9" 2.36' 1000 1.6 1550 9" 2.36' 950 2.
Fan Curves Zephyr Fans All Zephyr fan curves are based on laboratory tests conducted in accordance with AMCA standards. The curves shown below summarize the sizes and speeds of units available. TDA Models 0.600 0.550 0.550 0.500 Z3H - Z6H 0.450 0.400 0.350 0.300 Z6 S 0.250 Z3H 0.200 Z6 S 0.250 Z3H 0.200 0.150 H 40 0 80 160 120 CFM MAXIMUM WATTS FOR: MODEL Z3H – 39 MODEL Z5H – 79 200 0.100 0.000 240 1.625 1.625 1.500 1.500 Z8S - Z10H Z1 0S 1.125 Z8H 1.000 S Z8 Z8 0.
Sound Data Notes Zephyr Fans Since any mechanical power generates some sound energy into the air, fans will create some noise. Because of the great number of factors influencing sound output, it is invalid to compare fans based on RPM, tip speed or outlet velocity. The only accurate basis of comparison is the sound power level generated by the fan at the required point of operation. System designers use many methods to predict acoustic acceptability of an occupied space.
Engineering Notes Zephyr Fans The following section includes engineering and technical data, guidelines and system explanations related to air moving and control devices. Fan laws and system descriptions are consistent with industry standards, definitions and accepted practices. They are provided to assist system designers in sizing, selecting and defining their air moving and control systems as well as explaining variables inherent in system design. Handbook of Fundamentals and SMACNA Duct Design Manual.
Engineering Notes Zephyr Fans Effect Of Changes In Speed D = diameter c = change Increases or decreases in fan speed will alter the volume flow rate through a system. Figure 2 illustrates the increase in flow rate when the fan speed increases 10% to Point 2. The 10% increase in flow rate, however, extracts a severe power penalty. According to the fan laws (see below), the power increase is 33%. This fact is often startling to the system designer who finds a flow deficiency.
Engineering Data Zephyr Fans Figure 3 System Effect Figure 5 illustrates deficient fan/system performance resulting from one or more undesirable flow conditions. It is assumed that the system pressure losses, shown in system curve A, have been accurately determined, and a suitable fan selected for operation at Point 1. However, no allowance has been made for the effect of the system connections on the fan’s performance.
Engineering Data Zephyr Fans Outlet System Effect Factors Inlet Duct Elbows Non-uniform flow into a fan inlet is the most common cause of deficient fan performance. An elbow located at, or in close proximity to the fan inlet will not allow the air to enter the impeller uniformly. The result is less than cataloged air performance. Figure 6 To calculate 100% effective length, assume a minimum of 2 1/2 duct diameters for 2500 FPM or less. Add 1 duct diameter for each additional 100 FPM.
Suggested Specifications Zephyr Fans CEILING AND CABINET FANS shall be PennBarry Zephyrs manufactured by PennBarry, Richardson, Texas 75081. Fans shall have acoustically insulated galvanized steel housings and shall not exceed sound level ratings shown. Fans shall bear the AMCA Certified Ratings Seal and UL label. Integral backdraft damper (except Z14 and Z15) shall be chatter proof. Fans shall have true centrifugal wheel or wheels.
One Year Limited Warranty Zephyr Fans What Products Are Covered PennBarry Fans and Ventilators (each, a “PennBarry Product”) One Year Limited Warranty For PennBarry Products PennBarry warrants to the original commercial purchaser that the PennBarry Products will be free from defects in material and workmanship for a period of one (1) year from the date of shipment.
OTHER PENNBARRY PRODUCTS CENTRIFUGAL PRODUCTS Domex Fumex Fatrap Zephyr Dynamo Centrifugal Roof Exhausters Kitchen Hood Centrifugal Roof Exhausters Ceiling and Inline Fans Centrifugal Blowers Centrex Inliner LC Dynafan ESI Fume Exhaust Centrifugal Inline Fans Low Contour Centrifugal Roof Exhausters Efficient Silent Inline Fan Curb Mounted Centrifugal Fans AXIAL / GRAVITY PRODUCTS Breezeway HI-EX Tubeaxial Vaneaxial Propeller Wall Fans Power Roof Ventilator Inline Fans Inline Fans P