Z50 / Z70 v2 / Z100
https://www.zennio.com Tecnical Support: https://support.zennio.com
158
1558
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Internal Temp. Probe]
Overheating
0 = No Alarm; 1 = Alarm
1559, 1563, 1567, 1571
2
Bytes
O
C R - T -
DPT_Value_Temp
-273,00º - 670433,28º
[Ix] Current Temperature
Temperature Sensor Value
1560, 1564, 1568, 1572
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm; 1 = Alarm
1561, 1565, 1569, 1573
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm; 1 = Alarm
1562, 1566, 1570, 1574
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm; 1 = Alarm
1575
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
1576, 1614
2
Bytes
I
C - W T U
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Temperature Source 1
External Sensor Temperature
1577, 1615
2
Bytes
I
C - W T U
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Temperature Source 2
External Sensor Temperature
1578, 1616
2
Bytes
O
C R - T -
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Effective Temperature
Effective Control Temperature
1579, 1617
1 Byte
I
C - W - -
DPT_HVACMode
1=Confort
2=Standby
3=Económico
4=Protección
[Tx] Special Mode
1-Byte HVAC Mode
1580, 1618
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Comfort
0 = Off; 1 = On
1581, 1619
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Standby
0 = Off; 1 = On
1582, 1620
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Economy
0 = Off; 1 = On
1583, 1621
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Protection
0 = Off; 1 = On
1584, 1622
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[Tx] Window Status (Input)
0 = Closed; 1 = Open
1585, 1623
1 Bit
I
C - W - -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
1586, 1624
1 Byte
O
C R - T -
DPT_HVACMode
1=Confort
2=Standby
3=Económico
4=Protección
[Tx] Special Mode Status
1-Byte HVAC Mode
1587, 1625
2
Bytes
I
C - W - -
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Setpoint
Thermostat Setpoint Input
2
Bytes
I
C - W - -
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Basic Setpoint
Reference Setpoint
1588, 1626
1 Bit
I
C - W - -
DPT_Step
0/1
[Tx] Setpoint Step
0 = Decrease Setpoint; 1 =
Increase Setpoint
1589, 1627
2
Bytes
I
C - W - -
DPT_Value_Tempd
-671088,64º -
670433,28º
[Tx] Setpoint Offset
Float Offset Value
1590, 1628
2
Bytes
O
C R - T -
DPT_Value_Temp
-273,00º - 670433,28º
[Tx] Setpoint Status
Current Setpoint