User Guide
Table Of Contents
- Contents
- Document updates
- 1 Introduction
- 2 Configuration
- 2.1 General
- 2.2 Display
- 2.3 Inputs
- 2.4 Thermostat n
- ANNEX I. Video Intercom Operation
- ANNEX II. Internal Call Operation
- ANNEX III. Remote Control via IP
- ANNEX IV. Graphs
- ANNEX V. Differences with Z50 / Z100
- ANNEX VI. Communication Objects
Z50 / Z70 v2 / Z100
https://www.zennio.com Tecnical Support: https://support.zennio.com
145
ANNEX VI. COMMUNICATION OBJECTS
“Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Note: The number of instances of every functional block can vary between devices, as it is explained in the “ANNEX V. Differences with Z50 / Z100”
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
3
Bytes
I
C - W T U
DPT_TimeOfDay
00:00:00 - 23:59:59
[General] Time of Day
Time of Day External Reference
2
3
Bytes
I
C - W T U
DPT_Date
01/01/1990 -
31/12/2089
[General] Date
Date External Reference
3
1 Byte
C - - T -
DPT_SceneControl
0-63; 128-191
[General] Scenes: Send
0-63/128-191 (Run/Save Scene
1-64)
4
1 Byte
I
C - W - -
DPT_SceneNumber
0 - 63
[General] Scenes: Receive
0-63 (Run Scene 1-64)
5
1 Bit
I
C - W - -
DPT_State
0/1
[General] Activity
0 = Inactivity; 1 = Activity
6
1 Byte
I
C - W - -
Locale Enumeration
0 - 5
[General] Localization - Select
0 = Main; 1 = Conf. 2; ...; 4 =
Conf. 5
7
4
Bytes
I
C - W - -
1.xxx
0/1
[General] Localization - Select
Locale Selection Through ISO
639-1/ISO 3166-1 Four Letters
Code
8
2
Bytes
I
C - W - -
DPT_LanguageCodeAlpha2_ASCII
[General] Translations - Select
Language Selection Through ISO
639-1 Two Letters Code
9
1 Bit
I
C - W T U
DPT_Enable
0/1
[General] Touch Locking
0 = Unlock; 1 = Lock
1 Bit
I
C - W T U
DPT_Enable
0/1
[General] Touch Locking
0 = Lock; 1 = Unlock
10
2
Bytes
I
C - W T U
DPT_Value_Temp
-273,00º - 670433,28º
[General] External Temperature
Temperature to show in the
display
11
1 Bit
I
C - W T -
DPT_Ack
0/1
[General] Cleaning Function
0 = Nothing; 1 = Clean Now
12
1 Bit
O
C R - T -
DPT_Switch
0/1
[General] Welcome Back Object
Switch Object Sent on Wake Up
13, 14, 15, 16, 17
1 Bit
I
C - W - -
DPT_Switch
0/1
[General] Welcome Back Object
- Additional Condition
Additional Condition Object x
18
1 Bit
I
C - W T U
DPT_Switch
0/1
[General] Temperature Scale
0 = ºC; 1 = ºF
19, 25, 31, 37, 43, 49
1 Bit
I
C - W - -
DPT_Switch
0/1
[General][Pop-Up x] 1 Bit
0 = Hide Pop-Up; 1 = Show
Pop-Up
1 Bit
I
C - W - -
DPT_Switch
0/1
[General][Pop-Up x] 1 Bit
0 = Show Pop-Up; 1 = Hide
Pop-Up
20, 26, 32, 38, 44, 50
1 Byte
I
C - W - -
DPT_Value_1_Ucount
0 - 255
[General][Pop-Up x] 1 Byte
Hide/Show Pop-Up