Minimum Setpoint Value [-99 18 199][ºC]: minimum setpoint value that
the user can be set on the chronothermostat panel (see Figure 109).
Maximum Setpoint Value [-99 … 30 … 199][ºC]: maximum setpoint value that
the user can be set on the chronothermostat panel (see Figure 109).
Enablement [0 = Disable; 1 = Enable / 0 = Enable; 1 = Disable]: selects the
polarity of the control object "[Ci] Chronothermostat: Enable", which will
enable or disable the chronothermostat analogously as from the on-screen
switch button of the box (see Figure 108). The box configured as a
chronothermostat control looks as follows:
Figure 108. Chronothermostat box
The top button will enable the chronothermostat to be switched on or off, i.e. to resume
or stop the programmed sending. The programming of the timed actions will be
performed through the following pop-up window, visible by clicking on the bottom button:
Figure 109. Chronothermostat panel
Each box configured as a chrono-thermostat contains four pages with six customisable
timers each, being possible for the user to configure up to 24 timed actions.