NUMBER SIZE I/O FLAGS DATA TYPE (DPT)
VALUES
RANGE 1ST TIME RESET
NAME FUNCTION
2 Bytes O C T R – - [8.001] DPT_Value_2_Count -3276832767 0 Last
[PX][BX] 2-byte Signed Int
Control
-32768...32767
2 Bytes O C T R – - [7.001] DPT_Value_2_Ucount 0 – 65535 0 Last
[PX][BX] 2-byte Unsigned Int
Control
0...65535
1 Byte O C T R – - [5.001] DPT_Scaling 0 – 100 0 Last [PX][BX] Percentage Control 0-100%
1 Byte O C T R – - [6.010] DPT_Value_1_Count -128127 0 Last
[PX][BX] 1-byte Signed Int
Control
-128...127
1 Byte O C T R – - [5.010] DPT_Value_1_Ucount 0 – 255 0 Last
[PX][BX] 1-byte Unsigned Int
Control
0...255
1 Bit O C T R – - [1.001] DPT_Swi tch 0/1 0 Last [PX][BX] Binary Control 1-bit Control
10, 13, 16, 19, 22, 25,
28, 31, 34, 37, 40, 43,
46, 49, 52, 55, 58, 61,
64, 67, 70, 73, 76, 79,
82, 85, 88, 91, 94, 97,
100, 103, 106, 109, 112, 115,
118, 121, 124, 127, 130, 133,
136, 139, 142, 145, 148, 151
1 Bit O C T R – - [1.015] DPT_Reset 0/1 0 Last [PX][BX] Energy Monitor: reset 0=No Action; 1=Reset
1 Byte I/O
C T R W
U
[5.001] DPT_Scaling 0-100 0 Last [PX][BX] Blue Channel 0-100%
4 Bit O C T R – - [3.007] DPT_Control_Dimming 0-100 0 Last [PX][BX] Light Dimming 4-bit Dimming Control
1 Bit O C T R – - [1.007] DPT_Step 0/1 0 Last [PX][BX] Stop Shutter 0 or 1 -> Stop
152, 179 2 Bytes I C – - W - [9.001] DPT_Value_Temp -273.00 670760.00 25 Last [TX] Temperature Source 1 External Sensor Measure
153, 180 2 Bytes I C – - W - [9.001] DPT_Value_Temp -273.00 670760.00 25 Last [TX] Temperature Source 2 External Sensor Measure
154, 181 1 Byte I C – - W - [20.102] DPT_HVACMode
0=Confort;
1=Standby;
3=Economy;
4=Building Protection
0 Last [TX] Special Mode 1-byte HVAC Mode
155, 182
1 Bit I C – - W - [1.001] DPT_Switch 0/1 Paramet. Last [TX] Special Mode: comfort 0=Off; 1=On
1 Bit I C – - W - [1.017] DPT_Trigger 0/1 Paramet. Last [TX] Special Mode: comfort 0=Nothing; 1=Trigger
156, 183
1 Bit I C – - W - [1.001] DPT_Switch 0/1 Paramet. Last [TX] Special Mode: standby 0=Off; 1=On
1 Bit I C – - W - [1.017] DPT_Trigger 0/1 Paramet. Last [TX] Special Mode: standby 0=Nothing; 1=Trigger
157, 184
1 Bit I C – - W - [1.001] DPT_Switch 0/1 Paramet. Last [TX] Special Mode: economy 0=Off; 1=On
1 Bit I C – - W - [1.017] DPT_Trigger 0/1 Paramet. Last [TX] Special Mode: economy 0=Nothing; 1=Trigger
158, 185
1 Bit I C – - W - [1.001] DPT_Switch 0/1 0 Last [TX] Special Mode: protection 0=Off; 1=On
1 Bit I C – - W - [1.017] DPT_Trigger 0/1 0 Last [TX] Special Mode: protection 0=Nothing; 1=Trigger
159, 186 1 Bit I C – - W - [1.019] DPT_W indow_Door 0/1 0 Last [TX] Window Status (input) 0=Closed; 1=Open
160, 187 1 Bit I C – - W - [1.017] DPT_Trigger 0/1 0 Last [TX] Comfort Prolongation 0=Nothing; 1=Timed Comfort
161, 188 1 Byte O C T R – - [20.102] DPT_HVACMode
0=Confort;
1=Standby;
3=Economy;
4=Building Protection
0 Last [TX] Special Mode Status 1-byte HVAC Mode
162,189
2 Bytes I C – - W - [9.001] DPT_Value_Temp 5.00 45.00 Paramet. Last [TX] Basic Setpoint Reference setpoint
2 Bytes I C – - W - [9.001] DPT_Value_Temp 5.00 45.00 Paramet. Last [TX] Setpoint Thermostat setpoint input
163, 190 1 Bit I C – - W - [1.007] DPT_Step 0/1 0 Last [TX] Setpoint Step 0=-0.5ºC; 1=+0.5ºC
164, 191 2 Bytes I C – - W - [9.002] DPT_Value_Tempd -10.00 10.00 Paramet. Last [TX] Setpoint Offset Float offset value
165, 191 2 Bytes O C T R – - [9.001] DPT_Value_Temp 5.00 45.00 Paramet. Last [TX] Setpoint Status Current setpoint