User manual
InZennio Z41
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
53
Setpoint type: it may be absolute (default), relative (1-bit object) or
relative (float object).
If the first is selected, the control object will be a 2-byte floating point object
and its value will correspond to the actual setpoint value to be sent to the
thermostat, being progressively higher or lower as the user touches the
control buttons. On the other hand, the permitted setpoint temperatures
will be delimited by a maximum value and a minimum value, defined by
the so-named parameters.
Figure 49 Absolute setpoint control
If the second option is selected (1-bit object setpoint control), the control
object will be binary, and it will throw a “0” to the bus whenever the user
asks for a setpoint decrement, and a “1” when the user asks for an
increment. How much it is incremented or decreased after every order is
defined through the offset parameter (which accepts values between 1
and 255 tenths of a degree), thus permitting a consistent self-update of the
label in the box after every user press, although the status object will also
admit the reception of feedback from the bus, i.e., the updated absolute
setpoint value sent from the external thermostat.
Figure 50 Relative (1 bit) setpoint control
Finally, when “Relative (float object)” is selected, the control will send 2-
byte floating point values. However, these values will correspond to the
particular increment or decrement (or offset) to be applied each time. This
offset refers to a base temperature and will always be a multiple of 0.5ºC.
As the user touches the increase/decrease buttons in the box, this offset
will vary, always within a certain range defined through the Minimum
offset and Maximum offset parameters.










