User manual
InZennio Z41
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
49
Note: the list with all the icons available in Z41 can be found in the document
“Z41 Icon list”, downloadable from www.zennio.com.
g) Shutter control
Shutter controls permit sending move up, move down, stop or step shutter
orders to the KNX bus by pressing the buttons in the box. In addition, the box
will contain an indicator that will permanently show, as a percentage, the value
of the status object.
Figure 46 Shutter control
The only specific parameter for this function is:
Action: sets which of the two buttons will send the move up orders and
which the move down orders. Options are “Left Down, Right Up” (default)
and “Left Up, Right Down”.
Setting up a box as a shutter control enables three communication objects,
[Pn][Bi] Shutter position (1 byte), [Pn][Bi] Move shutter and [Pn][Bi] Stop
shutter (both, binary objects). The former acts as the status object, which
determines the value shown in the box; it will be necessary to link it to the
analogous object from the shutter actuator (as it does not get automatically
updated on user presses) so it receives the value 100% when the shutter is
completely down, and the value 0% when it is totally up. On their side, control
orders will be sent through one of the two remaining objects:
Orders to move the shutter up/down (completely) are sent through [Pn][Bi]
Move Shutter after a long press on the corresponding button. Value “0”
represents the move up order, while “1” represents the move down order.
Orders to perform a step movement (value “0” for steps up and “1” for
steps down) are sent through [Pn][Bi] Stop shutter after a short press on