User manual
InZennio Z41
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
29
measurement is found to be slightly over (or below) the actual temperature
due to external factors, it is possible to set an adjustment between -5.0ºC and
5.0ºC (0.0ºC by default), in steps of 0.1ºC. The value set here may be
optionally changed, in runtime, from the Configuration page (see section 2.4).
Sending period: cycle time (in tens of a second) for sending the value of the
measured temperature to the bus. This sending is made through the
[General] Internal temperature object (see section 3.1), enabled by default.
The permitted values are 0 to 100 tens of a second. The value “0” (set by
default) deactivates this sending to the bus.
Send with a temperature change: permits performing a specific sending of
the temperature value to the bus –through the [General] Internal
temperature object– whenever an increase or decrease greater or equal
than a certain value is detected between two consecutive measurements, no
matter if a periodic sending has been enabled or not. Such value (unsigned)
must be entered here, in terms of tenths of a degree. To avoid having this
extra sending on temperature changes, simply leave the value “0” (default
value).
3.2.5 ETHERNET
Figure 20 Ethernet (Main configuration)
The Ethernet screen, hidden by default, becomes visible once the corresponding
checkbox has been marked under the General screen (see section 3.2.1).
The Ethernet interface in Z41 is intended, at the moment, for updating the firmware of
the device (see section 1.3.1) across a local network. Alternatively, this process can be
performed through the built-in USB interface.