Operation Manual

Z41 Pro
http://www.zennio.com Tecnical Support: http://support.zennio.com
64
(with their Write and Read flags activated, so they can work as control and
status objects) named:
[Pn][Bi] Red Channel
[Pn][Bi] Green Channel
[Pn][Bi] Blue Channel
Control orders will consist in sending the light level (as a percentage) of
the different channels through the corresponding objects.
If the second option is selected, only one 3-byte object will be enabled:
[Pn][Bi] RGB Colour
In this case, the light levels of the three channels are sent (and received)
concatenated into the above 3-byte object.
Note: if statuses are received while the luminaire performs a regulation, this
control may become hardly serviceable until such regulation ends.
Left Button and Right Button: permit selecting the icon that will be
displayed inside the buttons in the box.
Note: a list with all icons available in Z41 Pro can be found in document “Z41
Pro Icon list”, available at www.zennio.com.
Regarding the RGB control boxes themselves, a central label will permanently
show, as a percentage, the current light level (which is determined by the
channel with the highest current light level). This indicator gets updated
automatically as the user interacts with the box, but is also conditioned by the
values received from the bus through the already described objects.
Figure 66 RGB (Box)
Moreover, two buttons can be found in the box: