Operation Manual

Z41 Pro
http://www.zennio.com Tecnical Support: http://support.zennio.com
50
Initial Value: sets which value from the permitted range will be assumed by
the control prior to any button presses. It is always 0 by default.
Minimum Value: sets which value from the available range will be the
minimum value permitted by the control after a number of presses on the
decrease button.
Maximum Value: sets which value from the available range will be the
maximum value permitted by the control after a number of presses on the
increase button.
Short Increment: sets the increase or decrease to be applied to the
current value on every short press over the increase or decrease buttons,
respectively (i.e., the smaller the increment is, the more presses will be
required). It is 1 by default, except for the case of the 2-byte floating point
control, where it is 0.5.
Long Increment: sets the increase or decrease to be applied to the current
value on every long press over the increase or decrease buttons,
respectively (i.e., the smaller the increment is, the more presses will be
required). It is 10 by default, except for the case of the 2-byte floating point
control, where it is 1.
Note: if the increments configured are too small, certain button touches may
not cause a perceptible value change on the indicator, due to precision
restrictions of the KNX standard.
f) Two-button Scene Control