Operation Manual

Z41 Lite
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
85
1 Bit
O
C T R - -
DPT_Trigger
0/1
[Ix] Presence: Slave Output
1 = Motion Detected
255, 279
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Ix] Presence Trigger
Binary Value to Trigger the Presence Detection
256, 280
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Ix] Presence: Slave Input
0 = Nothing; 1 = Detection from slave device
257, 281
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Ix] External Motion Detection
0 = Nothing; 1 = Motion detected by an external sensor
258, 263, 268,
282, 287, 292,
1 Byte O C T R - - DPT_Scaling 0% - 100%
[Ix] [Cy] Detection State
(Scaling)
0
-100%
259, 264, 269,
283, 288, 293
1 Byte O C T R - - DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] [Cy] Detection State
(HVAC)
Auto, Comfort, Standby, Economy, Building Protection
260, 265, 270,
284, 289, 294
1 Bit O C T R - - DPT_Switch 0/1
[Ix] [Cy] Detection State
(Binary)
Binary
Value
261, 266, 271,
285, 290, 295
1 Bit I C - - W - DPT_Switch 0/1
[Ix] [Cy] Channel Lock
According to parameters
262, 267, 272,
286, 291, 296
1 Bit I C - - W - DPT_Switch 0/1
[Ix] [Cy] Force State
0 = No Detection; 1 = Detection
297, 301
2 Bytes
O
C T R - -
DPT_Value_Temp
-273,00 - 670760,00
[Ix] Current Temperature
Temperature sensor value
298, 302
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm;1 = Alarm
299, 303
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm;1 = Alarm
300, 304
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm;1 = Alarm