Operation Manual

Z41 Lite
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
84
0xF (Inc. by 1%)
4 Bit
C T - - - DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
0x7 (Dec. by 1%)
0x8 (Stop)
0x9 (Inc. by 100%)
0xF (Inc. by 1%)
[Ix] [Long
Press]
Brighter/Darker
Long Pr.
-> Brighter/Darker; Release -> Stop
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Long Press] Dimmer ON
Sending of 1 (ON)
1 Bit
C T - - -
DPT_Switch
0/1
[Ix] [Long Press] Dimmer OFF
Sending of 0 (OFF)
1 Bit I C T - W - DPT_Switch 0/1
[Ix] [Long Press] Dimmer
ON/OFF
Switching 0/1
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Ix] [Long Press] Run Scene
Sending of 0 - 63
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Ix] [Long Press] Save Scene
Sending of 128 - 191
1 Bit O C T R - - DPT_Alarm 0/1
[Ix] [Switch/Sensor] Alarm:
Breakdown or sabotage
1 = Alarm; 0 = No Alarm
2 Bytes
C T - - - 9.xxx
-671088.64 -
670760.96
[Ix] [Long Press] Constant
Value (float)
Float value
2 Bytes
C T - - - DPT_Value_2_Ucount 0 - 65535
[Ix] [Long Press] Constant
Value (Integer)
0
- 65535
1 Byte
C T - - - DPT_Scaling 0% - 100%
[Ix] [Long Press] Constant
Value (Percentage)
0%
- 100%
1 Byte
C T - - - DPT_Value_1_Ucount 0 - 255
[Ix] [Long Press] Constant
Value (Integer)
0
- 255
239, 245 1 Bit
C T - - - DPT_Trigger 0/1
[Ix] [Long Press/Release] Stop
Shutter
Release
-> Stop Shutter
240, 246
1 Byte I C - - W - DPT_Scaling 0% - 100%
[Ix] [Long Press] Dimming
Status (input)
0%
- 100%
1 Byte I C - - W - DPT_Scaling 0% - 100%
[Ix] [Long Press] Shutter
Status (input)
0% = Top; 100% = Bottom
247
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Motion Sensor] Scene Input
Scene Value
248
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[Motion Sensor] Scene Output
Scene Value
249, 273
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] Luminosity
0-100%
250, 274
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Open Circuit Error
0 = No Error; 1 = Open Circuit Error
251, 275
1 Bit
O
C T R - -
DPT_Alarm
0/1
[Ix] Short Circuit Error
0 = No Error; 1 = Short Circuit Error
252, 276
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Ix] Presence State (Scaling)
0-100%
253, 277 1 Byte O C T R - - DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Ix] Presence State
(HVAC)
Auto, Comfort, Standby, Economy, Building Protection
254, 278
1 Bit
O
C T R - -
DPT_Occupancy
0/1
[Ix] Presence State (Binary)
Binary Value