Operation Manual

Z41 Lite
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
81
160, 187
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (input)
0=Closed; 1=Open
161, 188
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0=Nothing; 1=Timed Comfort
162, 189 1 Byte O C T R - - DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode Status
1
-byte HVAC Mode
163, 190
2 Bytes
I
C - - W -
DPT_Value_Temp
-273,00 - 670760,00
[Tx] Setpoint
Thermostat setpoint input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273,00 - 670760,00
[Tx] Basic Setpoint
Reference setpoint
164, 191
1 Bit
I
C - - W -
DPT_Step
0/1
[Tx] Setpoint Step
0=-0.5ºC; 1=+0.5ºC
165, 192
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760,00 -
670760,00
[Tx] Setpoint Offset
Float offset
value
166, 193
2 Bytes
O
C T R - -
DPT_Value_Temp
-273,00 - 670760,00
[Tx] Setpoint Status
Current setpoint
167, 194
2 Bytes
O
C T R - -
DPT_Value_Temp
-273,00 - 670760,00
[Tx] Basic Setpoint Status
Current basic setpoint
168, 195
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760,00 -
670760,00
[Tx] Setpoint Offset Status
Current setpoint offset
169, 196
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset setpoint to default
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Offset Reset
Reset offset
170, 197
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
171, 198
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
172, 199
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] On/Off
0=Off; 1=On
173, 200
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] On/Off Status
0=Off; 1=On
174, 201
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Cool)
PI Control (PWM)
175, 202
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Control Variable (Heat)
PI Control (PWM)
176, 203
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Cool)
PI Control (Continuous)
177, 204
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Heat)
PI Control (Continuous)
178, 205
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Cool
Temp >= (Setpoint+Band) => "1"
179, 206
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] Additional Heat
Temp <= (Setpoint-Band) => "1"
207, 211, 215,
219, 223, 227
2 Bytes
I
C - - W -
DPT_Power
-670760,00
670760,00
[Energy X] Power
kW
208, 212, 216,
220, 224, 228
4 Bytes
I
C - - W -
DPT_ActiveEnergy_kWh
-2147483648
2147483647
[Energy X] Energy
kWh
209, 213, 217,
221, 225, 229
2 Bytes I C - - W -
CO2 emission
(non-standardized
datapoint type)
-670760,00
670760,00
[Energy X] CO2
kg CO2
210, 214, 218,
222, 226, 230
2 Bytes I C - - W -
Currency
(non-standardized
datapoint type)
-670760,00
670760,00
[Energy X] Cost
Local Currency
231-234
1 Byte
I/O
C T R W U
DPT_Scaling
0% - 100%
[RGBW] White Channel 4
0-100%
235, 241
1 Bit
I
C - - W -
DPT_Switch
0/1
[Ix] Input Lock
1 = Locked; 0 = Unlocked