Operation Manual

Z41 Lite
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
79
1 = Heat
3 = Cool
9 = Fan
14 = Dry
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[Px][By] Fan Indicator
0-49%=Min; 50-100%=Max
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[Px][By] Fan Indicator
0-33%=Min; 34-66%=Med; >66%=Max
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[Px][By] Fan Indicator
0=Auto; 1-33%=Min; 34-66%=Med; >66%=Max
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[Px][By] Fan Indicator
0=Off; 1-33%=Min; 34-66%=Med; >66%=Max
1 Byte I C - - W U
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Px][By] Special Mode
Indicator
Comfort, Standby, Economy and Building Protection
1 Byte
I/O
C T R W U
DPT_Scaling
0% - 100%
[Px][By] Red Channel
0-100%
1 Bit
I
C - - W U
DPT_Enable
0/1
[Px][By] Alarm Trigger
Trigger
1 Bit
I
C - - W U
DPT_Alarm
0/1
[Px][By] Weekly Timer
Enabling
0 = Disabled; 1 = Enabled
1 Bit
I
C - - W U
DPT_Enable
0/1
[Px][By] Daily Timer Enabling
0 = Disabled; 1 = Enabled
1 Bit
I
C - - W U
DPT_Enable
0/1
[Px][By] RGB Color
Red, Green and Blue components
3 Bytes
I/O
C T R W U
DPT_Colour_RGB
[0 255] * 3
[Px][By] Chrono-thermostat:
enabling
0 = Disabled; 1 =
Enabled
10, 13, 16, 19,
22, 25, 28, 31,
34, 37, 40, 43,
46, 49, 52, 55,
58, 61, 64, 67,
70, 73, 76, 79,
82, 85, 88, 91,
94, 97, 100,
103, 106, 109,
112, 115, 118,
121, 124, 127,
130, 133, 136,
139, 142, 145,
148, 151
1 Bit
O
C T R - -
DPT_Switch
0/1
[Px][By] Binary Control
1-bit Control
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[Px][By] 1-byte Unsigned Int
Control
0...255
1 Byte
O
C T R - -
DPT_Value_1_Count
-128 - 127
[Px][By] 1-byte Signed Int
Control
-
128...127
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Px][By] Percentage Control
0-100%
2 Bytes
O
C T R - -
DPT_Value_2_Ucount
0 - 65535
[Px][By] 2-byte Unsigned Int
Control
0...65535
2 Bytes
O
C T R - -
-32768 - 32767
-32768 - 32767
[Px][By] 2-byte Signed Int
Control
-
32768...32767
2 Bytes
O
C T R - -
9.xxx
-671088,64
670760,96
[Px][By] 2
-byte Float Control
-
671088.64...670760.96
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[Px][By] Enumerated Control
0...255
1 Bit
O
C T R - -
DPT_UpDown
0/1
[Px][By] Move Shutter
0=Up; 1=Down
1 Bit
O
C T R - -
DPT_Switch
0/1
[Px][By] Light On/Off
0=Off; 1=On
2 Bytes
O
C T R - -
DPT_Value_Temp
-273,00 - 670760,00
[Px][By] Temperature Control
Absolute Float Value
2 Bytes
I/O
C T R W -
DPT_Value_Tempd
-670760,00 -
670760,00
[Px][By] Temperature Offset
Control
Relative Float Value
1 Bit
O
C T R - -
DPT_Step
0/1
[Px][By] Temperature Offset
Control
0=Decrease; 1=Increase
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Px][By] Mode Control
0 = Cool; 1 = Heat
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
[Px][By] Mode Control
Heat, Cool, Auto, Fan and Dry