When this function is assigned to the box, two 1-byte objects ([Pn][Bi] Special
Mode Control as the control object, and [Pn][Bi] Special Mode Indicator as
the status object) will be enabled. The former will be sending the bus the value
that corresponds to the mode that the user selects by touching the buttons (see
Table 6), while the status object (which can receive values from the bus
although it gets self-updated as well on button presses) will determine the
indicative icon represented in the box at any time. If this object receives an
unrecognised value from the bus, no icon will be displayed in the indicator.
Special Mode Icon Object Value
Comfort
1 (0x001)
Standby
2 (0x002)
Economy
3 (0x003)
Protection
4 (0x004)
Table 6 Special Modes vs. Icon vs. Object Value
The remaining parameters for this function are:
Allow Protection Mode: this parameter permits excluding (“No”, default
option) or including (“Yes”) the “building protection” mode from the special
modes listed in the sequential scrolling performed by the buttons.
Left Button and Right Button: permit selecting the icon that will be
displayed inside the buttons in the box.
Note: a list with all icons available in Z41 Lite can be found in document “Z41
Lite Icon list”, available at www.zennio.com.
3.4.2.5 OTHER
Figure 62 Other