Operation Manual

Z41 Lite
http://www.zennio.com Tecnical Support: http://zennioenglish.zendesk.com
53
“9” will be sent, and the setpoint will become 34ºC. And so on until an offset of “-10
(setpoint of 15ºC) is reached. From that moment, any further presses on the decrease
button will re-send the value “-10 and the setpoint will remain at 1C.
Important: the control object for the floating point relative setpoint control
has its Write flag enabled with the intention of permitting the reception of
feedback from the thermostat, which may reset or modify the status of the
offset for any reason at any time. This feedback allows that Z41 Lite
updates its own value to equal that from the external thermostat. Thinking
of the above example, if Z41 Lite receives the value 0after having the
user performed three presses on the increase button (therefore, after
having been sent the value “1.5to the bus), it will happen that on the forth
press the value sent will be “0.5and not 2”.
Figure 544 Relative (Float) Setpoint Control. Object Linking.
Note: the parameterised setpoint type becomes transparent to the final
user, as the aspect of the on-screen box remains the same in all cases. In
addition, the setpoint status object is always a 2-byte floating point object
and will represent, in any case, the absolute value of the current
temperature setpoint.
Left Button and Right Button: permit selecting the desired icon to be
displayed inside each button in the box.
Note: a list with all icons available in Z41 Lite can be found in document “Z41
Lite Icon list”, available at www.zennio.com.
b) Mode Control
This function turns the box into a climate mode control.
Z41
Lite
Thermostat
Control object
Status object
Offset
Offset (status)
Setpoint T. (status)