Operation Manual

Roll-ZAS
http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com
52
160, 161
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[Ix] Probe Error
1=Error;0=No Error
162, 164
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[Tx] Temperature Source 1
External Sensor Measure
163, 165
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[Tx] Temperature Source 2
External Sensor Measure
166, 167 1 Byte I
C - - W -
DPT_HVACMode
1=Comfort. 2=Standby
3=Economy
4=Protection
-
-
[Tx] Special Mode 1-byte HVAC Mode
168, 172
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: comfort
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: comfort
0=Off; 1=On
169, 173
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: standby
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: standby
0=Off; 1=On
170, 174
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: economy
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: economy
0=Off; 1=On
171, 175
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: protection
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: protection
0=Off; 1=On
176, 177
1 Bit
I
C - - W -
DPT_Window_Door
0/1
-
-
[Tx] Window Status (input)
0=Closed; 1=Open
178, 179
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Comfort Prolongation
0=Nothing; 1=Timed Comfort
180, 181 1 Byte O
C T R - -
DPT_HVACMode
1=Comfort. 2=Standby
3=Economy
4=Protection
- W
- W
[Tx] Special Mode Status 1-byte HVAC Mode
182, 183
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[Tx] Setpoint
Thermostat setpoint input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[Tx] Basic Setpoint
Reference setpoint
184, 185
1 Bit
I
C - - W -
DPT_Step
0/1
-
-
[Tx] Setpoint Step
0=-0.5ºC; 1=+0.5ºC
186, 187
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 - 670760.00
-
-
[Tx] Setpoint Offset
Float offset value
188, 189
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
- W
- W
[Tx] Setpoint Status
Current setpoint
190, 191
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
- W
- W
[Tx] Basic Setpoint Status
Current basic setpoint
192, 193
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 - 670760.00
- W
- W
[Tx] Setpoint Offset Status
Current setpoint offset
194, 195
1 Bit
I
C - - W -
DPT_Reset
0/1
-
-
[Tx] Setpoint Reset
Reset setpoint to default
1 Bit
I
C - - W -
DPT_Reset
0/1
-
-
[Tx] Offset Reset
Reset offset
196, 197
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
-
-
[Tx] Mode
0 = Cool; 1 = Heat
198, 199
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
- W
-
[Tx] Mode Status
0 = Cool; 1 = Heat
200, 201
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] On/Off
0=Off; 1=On
202, 203
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] On/Off Status
0=Off; 1=On
204, 206
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Cool)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Cool)
PI Control (PWM)
205, 207
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Heat)
PI Control (PWM)
208, 210
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
- W
- W
[Tx] Control Variable (Cool)
PI Control (Continuous)
209, 211
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
- W
- W
[Tx] Control Variable (Heat)
PI Control (Continuous)
212, 214
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Additional Cool
Temp >= (Setpoint+Band) => "1"