Operation Manual

Roll-ZAS
http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com
39
Periodical Sending of "0": defines the period, in seconds, for a cyclical
sending of the value "0" after the detection of the corresponding edge. Setting
this to 0 disables the periodical sending.
Periodical Sending of "1": defines the period, in seconds, for a cyclical
sending of the value "1" after the detection of the corresponding edge. Setting
this to 0 disables the periodical sending.
Lock: if "Yes" is chosen, a new 1-bit communication object, "[Ix] Lock", will
become visible, making it possible to lock and unlock the corresponding input
(with one "1" or one "0", respectively). During the time the input is locked, any
edges detected in the signal will be ignored.
Sending of Status on Bus Voltage Recovery: this option allows forcing an
automatic sending to the KNX bus of the state of the input line after a voltage
recovery, with a certain delay (value between 0 and 255, in seconds).
3.4.2 TEMPERATURE PROBE
Configuring an input as a temperature probe brings the following options.
Figure 22. Input: Temperature Probe
Temperature Sensor Calibration: setting a certain calibration (in tenths of a
degree) permits correcting the value received from the external temperature
sensor in case it is found to be altered for any reason and therefore different
to other available references, making it possible to synchronise both
references.
Temperature Sending Period: this is intended to set the period (in tens of a
second) for a cyclical sending to the KNX bus of the current temperature
value. Setting this to 0 indicates that no periodical sending will take place.
Send with a Temperature Change: apart from performing a periodical
sending, ZAS can send the bus the value of the current temperature