Number Size I/O Flags Data Type (DPT) Functional range 1st boot P Reboot P Name Function
4 = Protection
162, 189
2 Bytes I C - - W - DPT_Value_Temp -273.00 – 670760.00 -
-
[TX] Basic Setpoint Reference setpoint
2 Bytes I C - - W - DPT_Value_Temp -273.00 – 670760.00 -
-
[TX] Setpoint Thermostat setpoint input
163, 190 1 Bit I C - - W - DPT_Step 0/1 -
-
[TX] Setpoint Step 0=-0.5ºC; 1=+0.5ºC
164, 191 2 Bytes I C - - W - DPT_Value_Tempd
-670760.00 –
670760.00
-
-
[TX] Setpoint Offset Float offset value
165, 192 2 Bytes O C T R - - DPT_Value_Temp -273.00 – 670760.00 - W √
- W
[TX] Setpoint Status Current setpoint
166, 193 2 Bytes O C T R - - DPT_Value_Temp -273.00 – 670760.00 - W √
- W
[TX] Basic Setpoint Status Current basic setpoint
167, 194 2 Bytes O C T R - - DPT_Value_Tempd
-670760.00 –
670760.00
- W √
- W
[TX] Setpoint Offset Status Current setpoint offset
168, 195
1 Bit I C - - W - DPT_Reset 0/1 -
-
[TX] Offset Reset Reset offset
1 Bit I C - - W - DPT_Reset 0/1 -
-
[TX] Setpoint Reset Reset setpoint to default
169, 196 1 Bit I C - - W - DPT_Heat_Cool 0/1 -
-
[TX] Mode 0 = Cool; 1 = Heat
170, 197 1 Bit O C T R - - DPT_Heat_Cool 0/1 - W √
- W
[TX] Mode Status 0 = Cool; 1 = Heat
171, 198 1 Bit I C - - W - DPT_Switch 0/1 -
-
[TX] On/Off 0=Off; 1=On
172, 199 1 Bit O C T R - - DPT_Switch 0/1 - W √
- W √
[TX] On/Off Status 0=Off; 1=On
173, 200
1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Control Variable (Cool) PI Control (PWM)
1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Control Variable (Cool) 2-Point Control
174, 201
1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Control Variable (Heat) PI Control (PWM)
1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Control Variable (Heat) 2-Point Control
175, 202 1 Byte O C T R - - DPT_Scaling 0% - 100% - W
- W
[TX] Control Variable (Cool) PI Control (Continuous)
176, 203 1 Byte O C T R - - DPT_Scaling 0% - 100% - W
- W
[TX] Control Variable (Heat) PI Control (Continuous)
177, 204 1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Additional Cool Temp >= (Setpoint+Band) =>
"1"
178, 205 1 Bit O C T R - - DPT_Switch 0/1 - W
- W
[TX] Additional Heat Temp <= (Setpoint-Band) =>
"1"
206, 210, 214,
218, 222, 226
2 Bytes I C - - W - DPT_Power
-670760.00 –
670760.0
-
-
[Energy X] Power kW
207, 211, 215,
219, 223, 227
4 Bytes I C - - W - DPT_ActiveEnergy_kWh
-2147483648 –
2147483647
-
-
[Energy X] Energy kWh
208, 212, 216, 2 Bytes I C - - W - CO2 emission -670760.00 – -
-
[Energy X] CO2 kg CO2