Operation Manual

 InZennioZ41
http://www.zennio.com TecnicalSupport:http://zenniodeu tsch.zendesk.com
96
Number Size I/O Flags Data Type (DPT) Functional range 1st boot P Reboot P Name Function
82, 85, 88, 91,
94, 97, 100,
103, 106, 109,
112, 115, 118,
121, 124, 127,
130, 133, 136,
139, 142, 145,
148, 151
4 Bit O C T R - - DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
0x2 (Dec. by 50%)
0x3 (Dec. by 25%)
0x4 (Dec. by 12%)
0x5 (Dec. by 6%)
0x6 (Dec. by 3%)
0x7 (Dec. by 1%)
0x8 (Stop)
0x9 (Inc. by 100%)
0xA (Inc. by 50%)
0xB (Inc. by 25%)
0xC (Inc. by 12%)
0xD (Inc. by 6%)
0xE (Inc. by 3%)
0xF (Inc. by 1%)
-
-
[PX][BX] Blue Channel 0-100%
1 Byte I/O C T R W U DPT_Scaling 0% - 100% -
-
[PX][BX] Light Dimming 4-bit Dimming Control
1 Bit O C T R - - DPT_Reset 0/1 -
-
[PX][BX] Stop Shutter 0 or 1 -> Stop
152, 179 2 Bytes I C - - W - DPT_Value_Temp -273.,00 – 670760.00 25,00
-
[TX] Temperature Source 1 External Sensor Measure
153, 180 2 Bytes I C - - W - DPT_Value_Temp -273.00 – 670760.00 25,00
-
[TX] Temperature Source 2 External Sensor Measure
154, 181 1 Byte I C - - W - DPT_HVACMode
1 = Comfort
2 = Standby
3 = Economy
4 = Protection
-
-
[TX] Special Mode 1-byte HVAC Mode
155, 182
1 Bit I C - - W - DPT_Trigger 0/1 1
-
[TX] Special Mode: comfort 0=Off; 1=On
1 Bit I C - - W - DPT_Switch 0/1 1
-
[TX] Special Mode: comfort 0=Nothing; 1=Trigger
156, 183
1 Bit I C - - W - DPT_Trigger 0/1 -
-
[TX] Special Mode: standby 0=Off; 1=On
1 Bit I C - - W - DPT_Switch 0/1 -
-
[TX] Special Mode: standby 0=Nothing; 1=Trigger
157, 184
1 Bit I C - - W - DPT_Trigger 0/1 -
-
[TX] Special Mode: economy 0=Off; 1=On
1 Bit I C - - W - DPT_Switch 0/1 -
-
[TX] Special Mode: economy 0=Nothing; 1=Trigger
158, 185
1 Bit I C - - W - DPT_Trigger 0/1 -
-
[TX] Special Mode: protection 0=Off; 1=On
1 Bit I C - - W - DPT_Switch 0/1 -
-
[TX] Special Mode: protection 0=Nothing; 1=Trigger
159, 186 1 Bit I C - - W - DPT_Window_Door 0/1 -
-
[TX] Window Status (input) 0=Closed; 1=Open
160, 187 1 Bit I C - - W - DPT_Trigger 0/1 -
-
[TX] Comfort Prolongation 0=Nothing; 1=Timed Comfort
161, 188 1 Byte O C T R - - DPT_HVACMode
1 = Comfort
2 = Standby
3 = Economy
1 W
- W
[TX] Special Mode Status 1-byte HVAC Mode