Operation Manual

InZennio Z41
http://www.zennio.com Tecnical Support: http://support.zennio.com
91
Number
Size
I/O
Flags
Data Type (DPT)
Functional range
Name
Function
94, 97, 100,
103, 106, 109,
112, 115, 118,
121, 124, 127,
130, 133, 136,
139, 142, 145,
148, 151
0x4 (Dec. by 12%)
0x5 (Dec. by 6%)
0x6 (Dec. by 3%)
0x7 (Dec. by 1%)
0x8 (Stop)
0x9 (Inc. by 100%)
0xA (Inc. by 50%)
0xB (Inc. by 25%)
0xC (Inc. by 12%)
0xD (Inc. by 6%)
0xE (Inc. by 3%)
0xF (Inc. by 1%)
1 Byte
I/O
C T R W U
DPT_Scaling
0% - 100%
[PX][BX] Light Dimming
4-bit Dimming Control
1 Bit
O
C T R - -
DPT_Reset
0/1
[PX][BX] Stop Shutter
0 or 1 -> Stop
152, 179
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.,00
670760.00
[TX] Temperature Source 1
External Sensor Measure
153, 180
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 670760.00
[TX] Temperature Source 2
External Sensor Measure
154, 181 1 Byte I C - - W - DPT_HVACMode
1 = Comfort
2 = Standby
3 = Economy
4 = Protection
[TX] Special Mode
1-byte HVAC Mode
155, 182
1 Bit
I
C - - W -
DPT_Trigger
0/1
[TX] Special Mode: comfort
0=Off; 1=On
1 Bit
I
C - - W -
DPT_Switch
0/1
[TX] Special Mode: comfort
0=Nothing; 1=Trigger
156, 183
1 Bit
I
C - - W -
DPT_Trigger
0/1
[TX] Special Mode: standby
0=Off; 1=On
1 Bit
I
C - - W -
DPT_Switch
0/1
[TX] Special Mode: standby
0=Nothing; 1=Trigger
157, 184
1 Bit
I
C - - W -
DPT_Trigger
0/1
[TX] Special Mode: economy
0=Off; 1=On
1 Bit
I
C - - W -
DPT_Switch
0/1
[TX] Special Mode: economy
0=Nothing; 1=Trigger
158, 185
1 Bit
I
C - - W -
DPT_Trigger
0/1
[TX] Special Mode: protection
0=Off; 1=On
1 Bit
I
C - - W -
DPT_Switch
0/1
[TX] Special Mode: protection
0=Nothing; 1=Trigger
159, 186
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[TX] Window Status (input)
0=Closed; 1=Open
160, 187
1 Bit
I
C - - W -
DPT_Trigger
0/1
[TX] Comfort Prolongation
0=Nothing; 1=Timed Comfort
161, 188 1 Byte O C T R - - DPT_HVACMode
1 = Comfort
2 = Standby
3 = Economy
4 = Protection
[TX] Special Mode Status
1-byte HVAC Mode
162, 189
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 670760.00
[TX] Basic Setpoint
Reference setpoint