Operation Manual

InZennio Z41
http://www.zennio.com Tecnical Support: http://support.zennio.com
88
ANNEX II. COMMUNICATION OBJECTS
Functional rangeshows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular
meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data Type (DPT)
Functional range
Name
Function
0
3 Bytes
I/O
C T R W U
DPT_TimeOfDay
0:00:00 23:59:59
[General] Time
Current Time
1
3 Bytes
I/O
C T R W U
DPT_Date
01/01/1990 -
31/12/2089
[General] Date
Current Date
2
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[General] Scenes: send
Scene Value
3
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 670760.00
[General] Internal Temperature
Current Temperature (built-in sensor)
4
2 Bytes
I
C - - W U
DPT_Value_Temp
-273.00 670760.00
[General] External Temperature
Temperature to show in the display
5
1 Bit
I
C - - W -
DPT_Ack
0/1
[General] Illumination
0=No action; 1=Light Display
6
1 Bit
I
C - - W -
DPT_Switch
0/1
[General] Touch Lock
0=Touch disabled; 1=Touch enabled
1 Bit
I
C - - W -
DPT_Switch
0/1
[General] Touch Lock
0=Touch enabled; 1=Touch disabled
7
1 Bit
O
C T R - -
DPT_Switch
0/1
[General] Welcome Object
1-bit Generic Control
8, 11, 14, 17,
20, 23, 26, 29,
32, 35, 38, 41,
44, 47, 50, 53,
56, 59, 62, 65,
68, 71, 74, 77,
80, 83, 86, 89,
92, 95, 98, 101,
104, 107, 110,
113, 116, 119,
122, 125, 128,
131, 134, 137,
140, 143, 146,
149
1 Bit
I
C - - W U
DPT_Switch
0/1
[PX][BX] RGB Colour
Red, Green and Blue components
1 Byte
I
C - - W U
DPT_Value_1_Ucount
0 - 255
[PX][BX] Daily Timer Enabling
0 = Disabled; 1 = Enabled
1 Byte
I
C - - W U
DPT_Value_1_Ucount
0 - 255
[PX][BX] Weekly Timer Enabling
0 = Disabled; 1 = Enabled
1 Bit I C - - W U DPT_Enable 0/1
[PX][BX] Chrono-thermostat:
enabling
0 = Disabled; 1 = Enabled
1 Byte
I
C - - W U
DPT_Value_1_Count
-128 - 127
[PX][BX] Alarm Trigger
Trigger
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[PX][BX] Red Channel
0-100%
2 Bytes I C - - W U
DPT_Value_2_Ucount 0 - 65535
[PX][BX] Special Mode Indicator
Comfort, Standby, Economy and
Building Protection
2 Bytes I C - - W U
DPT_Value_2_Count -32768 - 32767
[PX][BX] Fan Indicator
0=Off; 1-33%=Min; 34-66%=Med;
>66%=Max
2 Bytes
I
C - - W U
9.xxx -671088.64
[PX][BX] Fan Indicator
0=Auto; 1-33%=Min; 34-66%=Med;