Operation Manual

InZennio Z41
http://www.zennio.com Tecnical Support: http://support.zennio.com
72
Timer Type Selector: two-button control that permits switching through the
following options:
Timer inactive. Timer active (every day).
Timer active
(no repetition).
Timer active
(countdown).
Time Selector: depending on the selected timer type, permits setting the
time for the automated sending, or the length of the countdown.
Value to be Sent: in case of having parameterised the sending of a binary
value, this control lets the user determine the concrete value to be sent
(“OFF” or “ON”). In the case of the sending of a scene, this control is not
shown, as the scene number is set by parameter.
Hence, at the time set by the user or once the countdown ends, the bus will be
automatically sent the corresponding value, through the [Pn][Bi] Daily Timer
Control object (for binary values) or through the [General] Scenes: Send
object (in case of scene values). In both cases the [Pn][Bi] Daily Timer
Enabling binary object will be available, making it possible to disable (by
sending the value “0”) or to enable (value “1”) the execution of the timed
sending set by the user. By default, timed sending is always enabled.
Note: in case of disabling a sending through [Pn][Bi] Daily Timer Enabling,
the corresponding box will show the “forbidden” icon, although the box will not
lose the configuration previously set by the user.
Finally, this function offers the following parameters in ETS:
Timer Type: switches between “1-bit value” (default option) andScene”.
Scene Number: shown only after selecting “Scene for the above
parameter. This field defines the number of the scene (1-64) that will be
sent to the bus on the execution of the timed sending.
e) Weekly Timer
Boxes configured as weekly timers let the final user program a timed sending of
a binary or scene value to the bus (according to the parameterisation) at a