permanently displays the value of a certain communication object, which is
enabled when the function is assigned to the box.
Function Range Related object
1-byte (unsigned int.) 0– 255 [Pn][Bi] 1-byte unsigned int indicator
1-byte (signed int.) -128 – 127 [Pn][Bi] 1-byte signed int indicator
Percentage indicator 0% – 100% [Pn][Bi] Percentage indicator
2-byte (unsigned int.) 0 – 65535 [Pn][Bi] 2-byte unsigned int indicator
2-byte (signed int.) -32768 – 32767 [Pn][Bi] 2-byte signed int indicator
2-byte (floating point) -671088.64 – 670760.96 [Pn][Bi] 2-byte float indicator
Table 2 Numerical indicators
The table contains the allowed value ranges and the name of the object for
each case.
Figure 35 1-Byte Indicator (Unsigned Integer)
In the particular case of the 2-byte floating point indicator, the integrator will be
shown a text field (Float Unit), empty by default, that permits specifying the
measuring units (up to 6 characters) of the displayed value, for instance “ºC”.
Moreover, for this particular case, Z41 will dynamically adjust the number of the
decimal figures shown depending on the order of magnitude of the current
value: two for values greater than 0 and lower than 0.1; one for values between
0.1 and 100; and none for other cases (and analogously for negative values).
All these numerical indicators implement an additional parameter, Save Log?.
In case of enabling this option (“Yes”), any changes in the value of the indicator
will be continuously saved to an internal log file, so the final user can be
afterwards offered a visual representation that reflects the chronological
evolution of such value. Boxes for which this option has been enabled will show
a small icon overlaid on their upper left corner.