download. The final user will have the option to switch the scheme from the
Profile page (see section 2.3), unless such option is disabled by parameter.
Show Time: sets whether the current time (according to the internal clock)
should show in the upper left corner of every page. The default is “Yes”.
Screen Illumination: lets defining whether the backlight should behave
during inactivity according to section 2.5 (Turn off screen), or if on the
contrary the screen should never turn off entirely (Attenuate the screen) or
not even attenuate the light level (Max illumination always).
Note: the default option is encouraged. Permanent illumination may affect
adversely the device lifetime, and is only intended for special circumstances.
Show Temperature: sets whether the current temperature should show or
not in the upper right corner of every page, being necessary in such case to
choose the source of the temperature value: “Internal temperature probe” or
“External value”. If the latter is chosen, an object named [General] External
temperature will be enabled, so that it can be grouped with any other object
that sends temperature values.
Time/Date Sending Period: when enabled (value different from zero),
whenever the device is restarted, the date and time objects (“[General] Date
and “[General] Time”) will be sent to the bus, and thereafter, they will be sent
again every time the period expires. Setting a new time to the device either
through object or from the date/time configuration window will not restart the
count of the sending period. Range: [0-65535] x 1 min. The default is 10 min.
Note: to prevent time lags, it is advisable to only have one master clock within
the installation. Having multiple devices overwriting each other their time and
date registers periodically may end up inducing delays
Thermostat 1: checkbox (unselected by default) that activates/deactivates
the Thermostat 1 parameter screen. See section 3.7.
Thermostat 2: idem for Thermostat 2. See section 3.7.
Weekdays Initials (Mon...Sun): field that permits customising the label that
represents each of the weekdays within the configuration pages of the weekly
timers (see epigraph e) in section 3.4.2.5). A 7-character string (including