Operation Manual
ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com
49
SECTION
NUMBER
SIZE
IN/OUT
FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1st
TIME
RESET
INPUTS
178-185
(ODD)
1 bit, 4 bits,
1 byte
O
WT
-
-
-
[Ix] [Long Press] Move Up/Down Shutter
Long Pr. -> Switching "0/1"
[Ix] [Long Press] Stop/Step Up Shutter
Long Pr. -> Sending of "0"
[Ix] [Long Press] Stop/Step Down Shutter
Long Pr. -> Sending of "1"
[Ix] [Long Press] Stop/Step Shutter (switched)
Long Pr. -> Switching "0/1"
[Ix] [Long Press] Dimmer ON
Long Pr. -> Sending of 1 (ON)
[Ix] [Long Press] Dimmer OFF
Long Pr. -> Sending of 0 (OFF)
[Ix] [Long Press] Dimmer ON/OFF
Long Pr. -> Switching "0/1"
[Ix] [Sensor] Edge
Edge -> Sending of "0" or "1"
THERMOSTAT
186-187
2 bytes
I
W
-40ºC –
150ºC
25ºC
Last
[T1] Temperature source x (x=1,2)
External sensor measure
188-189
2 bytes
I
W
-40ºC –
150ºC
25ºC
Last
[T2] Temperature source x (x=1,2)
External sensor measure
190-191
1 byte
I
W
1-4
Parame
ter.
Parameter.
[Tx] Special Mode:
1-byte HVAC mode
192-199
1 bit
I
W
0/1
0
Last
[Tx] Special Mode: x (x= Comfort, Standby,
Economy or Protection)
0=Nothing; 1=Trigger
1 bit
I
W
0/1
0
Last
[Tx] Special Mode: x (x= Comfort, Standby,
Economy or Protection)
0=Off; 1=On
200-201
1 bit
I
W
0/1
0
Last
[Tx] Window status (input)
0=Closed; 1=Opened
202-203
1 bit
I
W
0/1
0
0
[Tx] Comfort prolongation
0=Nothing; 1=Timed Comfort
204-205
1 byte
O
RT
0-255
Parame
ter.
Last
“[Tx] Special Mode (Status)
1-byte HVAC mode
W
[Tx] Consigna básica
Consigna de referencia
206-207
2 bytes
I
W
-20ºC –
150ºC
Parame
ter.
Last
[Tx] Basic setpoint
Reference setpoint:
[Tx] Setpoint
Thermostat Setpoint input
208-209
1 bit
I
W
0/1
0
Indifferent
[Tx] Setpoint (Step)
0=-0.5ºC;1=+0.5ºC
210-211
2 bytes
I
W
-10ºC, 10ºC
0
Last
[Tx] Setpoint (Offset)
Float value
212-213
2 bytes
O
RT
-20ºC –
150ºC
25ºC
Last
[Tx] Setpoint (Status)
Current setpoint
214-215
2 bytes
O
RT
-20ºC –
150ºC
Parame
ter.
Last
[Tx] Basic Setpoint (Status)
Current basic setpoint
216-217
2 bytes
O
RT
-10ºC, 10ºC
0
Last
[Tx] Setpoint (Offset Status)
Current setpoint offset
218-219
1 bit
I
W
0/1
0
Indifferent
[Ix] Setpoint reset
Reset setpoint to default
1 bit
I
W
0/1
0
Indifferent
[Tx] Offset Reset
Reset offset
220-221
1 bit
I
W
0/1
Parame
ter.
Last
[Tx] Mode
0=Cool; 1=Heat
222-223
1 bit
O
RT
0/1
Parame
ter.
Last
[Tx] Mode (Status)
0=Cool; 1=Heat
224-225
1 bit
I
W
0/1
Parame
ter.
Parameter.
[Tx] ON/OFF
0=Off; 1=On
226-227
1 bit
O
RT
0/1
Parame
ter.
Parameter.
[Tx] ON/OFF (Status)
0=Off; 1=On
228, 230
1 bit
O
RT
0/1
0
Last
[Tx] Control variable (Cool)
PI control (PWM)
[Tx] Control variable (Cool)
2-point control
229, 231
1 bit
O
RT
0/1
0
Last
[Tx] Control variable (Heat)
PI control (PWM)
[Tx] Control variable (Heat)
2-point control
232.234
1 byte
O
RT
0-100%
0
Last
[Tx] Control variable (Cool)
PI control (Continuous)
233.235
1 byte
O
RT
0-100%
0
Last
[Tx] Control variable (Heat)
PI control (Continuous)
236.238
1 bit
O
RT
0/1
0
Last
[Tx] Additional Cool
Temp > (Setpoint+Band) => "1"
237.239
1 bit
O
RT
0/1
0
Last
[Tx] Additional Heat
Temp < (Setpoint-Band) => "1"