Operation Manual

ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com
42
42
a) Short press
No action: Z38i does not carry out any action when short pressing over the push button
connected to its input.
Sending of 0/1: this function results on sending to the KNX bus a binary value, which will
change depending on the chosen option:
Response 0: sends the value "0" through the object "[Ix][Short Press] 0"
Response 1: sends the value "1" through the object "[Ix][Short Press] 1"
Response Switching 0/1: sends the values "0" and "1" alternately with every short
press through the object "[Ix][Short Press] Switching".
Shutter control: This function results on sending 1 bit to the bus, in order to control the
shutters. The available options are:
Up: Rise the shutter. The value "0” is sent trough the object “[Ix][Short Press] Move
Up Shutter”.
Down: Lower the shutter. The value "1” is sent trough the object “[Ix][Short Press]
Move Down Shutter”.
Up/Down (switched): Alternative switching between the Move Up/Down orders (to
manage the shutter with an only input), through the object "[Ix][Short Press] Move
Up/Down Shutter".
Stop/Step up: Stops the shutter; When talking about shutters with lamellas, this
mode allows the user to control them; this parameter moves lamellas a pull up step. The
value "0” is sent trough the object “[Ix][Short Press] Stop/Step Down Shutter”.
Stop/Step down: Stops the shutter. When talking about shutters with lamellas, this
mode allows the user to control them; this parameter moves lamellas a pull down step.
The value "1” is sent trough the object “[Ix][Short Press] Stop/Step Down Shutter”.
Stop/Switched Step: Stops the shutter. When talking about shutters with lamellas,
this mode allows the user to control them; this parameter alternatively switches the
lamellas pull up and down steps, by sending the values "0" and "1" alternately through the
object "[Ix][Short Press] Stop/Step Shutter (switched)".