Absolute temperature: the objects “[Clima x] Setpoint Sending and “[Clima x]
Setpoint Reception” are enabled, to send and receive, respectively, the setpoint
temperature to be set and the current setpoint of the climate system. Short or long
pressings over the box are allowed to set the desired setpoint (the temperature will
change in 0.5ºC to 0.5ºC, no matter the type of pressing). It is necessary to set a
lower and upper limits, in ºC, for the setpoint temperature. This way, the temperature
range of the control can be bounded. The indicator of the box will show the current
setpoint temperature.
Temperature offset: the same objects as before are enabled, but now it is sent to the
climate system an increase/decrease of the current setpoint temperature in an offset
value (in ºC) configured by parameter. After every pressing, short or long, the
setpoint value will be updated with the new offset. In the box, the indicator will show
the current offset value.
1-bit object: the 1-bit object "[Clima x] Setpoint Offset sending" is enabled, in
order to increment ("1") or decrement ("0") the value of the current setpoint in an
offset value (in tenths of degree) configured by parameter. Only short pressings are
available. After every pressing, the order to increment or decrement the current
setpoint value will be sent to the climate system. The box indicator will show the
established setpoint value, plus/minus the parameterized offset value. In case, the
communication object associated to the indicator is linked, via a same group address,
to the setpoint status object, it will be shown in the panel the current setpoint,
plus/minus the established offset value.
BOX 3 (Mode): Allows choosing the functioning mode of the Climate System. There
are two possible options to configure
Cool/Heat
Auto/Heat/Dry/Fan/Cool
Note: This second option can only be selected to control Air Conditioning Systems.
Depending on the selected option, one of these pairs of communication objects will be
enabled:
For the Cool/Heat configuration: the 1-bit objects “[Clima x] Mode Sending” and
“[Clima x] Mode Reception”. Via the object “Mode Sending”, the value of the current