Operation Manual
ZENNiO AVANCE Y TECNOLOGÍA vwww.zennio.com
22
22
Control type: to select the climate function to be controlled:
Mode type: Cool-Heat or Auto-Heat-Dry-Fan-Cool
Fan: the indicator type can be selected (no indicator, percentage or integer).
Swing
Icon: A pair of icons can be associated to the page box.
Note: Depending on the selected option, a communication object associated to the specific
box will appear in the ETS environment; the same object type corresponding the selected
option. This characteristic allows controlling also external climate systems.
1 byte control: This is a generic control to communicate all those devices susceptible to
be, by sending a single byte (value in the range 0 - 255) through the object "[Home x; Box y] 1
byte control".
Type: Three possible options available in this case:
Fixed value (one button, no indicator): By pressing the button on the display,
the same value will always be sent; the value selected in the field “Value”.
Percentage (2 buttons with indicator): to send a percentage, according to the
type of press (Short press: raise or lower 1% with every short key press; Long press:
raise or lower 10% with every long key press).
Note: Take into account that value 0 corresponds with 0% and value 255 with 100%.
Value 0-255 (2 buttons with indicator): to send a value between 0 and 255,
according to the type of press (Short press: raise or lower one single point in the
range with every short key press; Long press: raise or lower 10 points in the range
with every long key press).