The timing cables must be properly wired in order for the timing signal to be
transmitted from one Location Sensor to the other. It is recommended that
this test be completed on each cable by the installer prior to operation. This
test requires quantity 2 four pair to two pair connector adapters ZES p/n
21204, and a Fluke 620 CableMeter. Brief instructions are provided below;
consult the Fluke CableMeter instruction manual for detailed instructions.
Setup
Connect adapter #1 between the Fluke 620 CableMeter and the near end of the
cable to be tested. Connect the Fluke Cable ID unit and adapter #2 to the far
end of the cable to be tested using a RJ-45 coupler.
Figure 38 Test setup for CAT5 cable
using Fluke 620
8.3.3 Timing Cable Test Procedure
2 pair adapters
Cable
under test