7.2 Power, AC
The customer must provide 100-240 Vac power 50/60 Hz to the specified
Location Sensor position. The Location Sensor units require DC 36-57V,
350mA for operation. The power supply used must be ZES approved. The
recommended power supply, which is shipped with the Location Sensor, has a
6 ft (2 m) AC cable and a 6 ft (2 m) dc cable. The electrician should verify
that the AC power is available within 6 ft (2 m) of the position of the Location
Sensor. This allows a 6 ft (2 m) “service loop” margin if the Location Sensor
position must be readjusted after the AC power is installed.
The Location Sensor must always be used with the specified power supply
available from ZES. The use of a different power supply could result in
equipment damage and/or electric shock or fire hazard.
Two optional 50 ft (15 m) dc power extension cables are available for
installations in which it is not desirable to rout the AC power within 6 ft (2 m)
of the Location Sensor. One is for indoor use only and is Plenum Rated, ZES
Part Number PX-010-00. The other is an outdoor rated (UV stable), ZES
Part Number PX-050-00. Consult your ZES Account Manager for
recommended wire size if additional lengths are required for a particular
installation.
Power Supplies have a limited safe operating temperature rating, please
check with ZES account representative concerning limitations or
availability of extend temperature range power supply, such as PS-TDB-
00. In outdoor installations the power supply must be installed within a
suitable waterproof housing per applicable building codes. The use of a
non qualified housing could result in equipment damage and/or electric
shock or fire hazard.