Using your ZebraStat (continued)
Activate - This mode is like having a remote-
control thermostat. Technicians often use it
when the thermostat is not easily accessible:
when making a diagnosis or repair to a unit in
an attic, basement, roof, or new construction
where the thermostat hasn't been installed yet.
2) Hook-Up. Start with the Mode Switch in the
ANALYZE position and have all component
switches OFF. The hookup of Zebra-Stat’s
leads is the same for all modes. First, connect
the component lead’s alligator clips to their re-
spective wires at the equipment. (Common uses
of wire colors are listed below the component
switches. However, you can use any of the wires
to test any other 24V function, like ‘Emergency
Heat’.) Then connect the Red and Blue leads
to the equipment’s 24V power, observing polar-
ity. All modes except ANALYZE require that all
thermostat functions be OFF.
3) & 4) Manipulate Controls & Observe LED’s
& Equipment. See the following sections (
Con-
tinuity, Analysis, or Activation) for the proper
steps to follow next.
5