User manual

VER. 001_16.09.2009
TRANSFORMERS TRM-8, -12, -24, -358
INSTRUCTION MANUAL
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: marketing@zamel.pl
FEATURES
DESCRIPTION
Electronic systems supply
used as bells and doorchimes trans-
formers,
short circuits and overloads resi-
stant,
inner thermal protection,
threemodular casing,
TH-35 DIN rail or surface mounting.
Transformers are used to supply
electronic systems where it is required
to lower voltage value to the appropriate
level. The universal casing enables mo-
unting on the TH-35 DIN rail or on the
surface. Available versions of secondary
voltage: 8 V AC, 12 V AC, 24 V AC and
3 V AC, 5 V AC, 8 V AC.
The device is designed
for single-phase installa-
tion and must be installed
in accordance with stan-
dards valid in a particular
country. The device should
be connected according to
the details included in this operating ma-
nual. Installation, connection and con-
trol should be carried out by a qualied
electrician staff, who act in accordance
with the service manual and the device
functions. Disassembling of the device is
equal with a loss of guarantee and can
cause electric shock. Before installation
make sure the connection cables are
not under voltage. The cruciform head
screwdriver 3,5 mm should be used to
instal the device. Improper transport,
storage, and use of the device inuence
its wrong functioning.
It is not advisable to instal the device in
the following cases: if any device part is
missing or the device is damaged or de-
formed. In case of improper functioning
of the device contact the producer.
CAUTION
TECHNICAL DATA
Parameters for all transformers TRM-XXX
Rated primary voltage: 230 V AC
Rated frequency: 50 / 60 Hz
Rated power: 15 VA
Rated surrounding temperature: +40
o
C
Average increase coil temperature admissible: 80
o
C
Number of terminal clamps: 4 (6 for TRM-358)
Protective class: II
Thermal insulation class: B (120
o
C)
Operating mode: continuous
Section of connecting cables: 0,2 ÷ 2,50 mm
2
Operating position: free
Mounting: TH35 rail (PN-EN 60715) or surface
Protection degree: IP20 (PN-EN 60529)
Overvoltage category: II
Pollution degree: P2
Rated impulse withstand voltage: 2,1 kV
Dimensions (height / width / depth): threemodular (53 mm) 90x53x66 mm
Weight: 0,474 kg
Reference standards: PN-EN 61558-1, PN-EN 61558-2-6
TRM-8
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 9,6 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 1,88 A AC
Rated secondary voltage: 8 V AC
Rated secondary voltage tolerance: ±5 %
TRM-12
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 14,4 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 1,25 A AC
Rated secondary voltage: 12 V AC
Rated secondary voltage tolerance: ±5 %
TRM-24
No-load state current: maks. 32 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 28,7 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 0,625 A AC
Rated secondary voltage: 24 V AC
Rated secondary voltage tolerance: ±5 %
TRM-358
No-load state current: maks. 36 mA AC (U=230 V AC, f=50 Hz)
No-load state secondary voltage: 3,9 V AC or 6,3 V AC or 9,8 V AC
No-load state secondary voltage tolerance: ±5 %
Rated secondary current: 5 A AC or 3 A AC or 1.88 A AC
Rated secondary voltage: 3 V AC or 5 V AC or 8 V AC
Rated secondary voltage tolerance: ±10 %
NOTE: Minimum distance to the other devices - 10 mm
The symbol means selective
collecting of electrical and electronical
equipment. It is forbidden to put
the used equipment together
with other waste

Summary of content (2 pages)