User`s manual

BL160052 s System Development
Add termination and
bias resistors on the
master controller only
BL1600
BL1600
BL1600
BL1600
Add a termination
resistor on the
end controller
No termination or
bias resistors on
other controllers
RS-485 Network Hardware Connections
Figure 4-10 and Figure 4-11 show the connections for a two-wire RS-485
network. Remove RP2, shown in Figure 4-12, from all BL1600 controllers
in the network, except the BL1600 that is the master controller. RP2
contains the bias and termination resistors. Add a 220 termination
resistor to the end BL1600 as shown in Figure 4-12.
Figure 4-10. RS-485 Multidrop Network