Technical information

DRV Operator’s Manual and Technical Reference (rev 1 0 June 30, 2000)
B.1 Introduction
The DRV utilizes an industrial controller. The controller has two types of inputs, analog
and digital. The analog inputs are accomplished via the analog to digital (A-D)
expansion board. The A-D board converts a varying input voltage into a digital integer
value that the controller can use to evaluate signal amplitude. As an example, +5 Volts
may be represented as the integer value 2048 in software. Likewise, there are two types
of outputs, digital and analog. The analog outputs are accomplished via the digital to
analog (D-A) expansion board. The conversions are done in hardware and interpreted in
software. Digital inputs and outputs (IO) are accomplished with the digital IO interface
on the controller and the digital IO expansion board. The digital I/O utilizes Transistor-
Transistor Logic (TTL). Voltage readings should always be done with a digital
voltmeter. Using a test light or jumpers could cause damage to the controller. A
qualified person should be dedicated to the emergency stop switch before any testing is
conducted.
B.1.1 Analog Inputs
The joystick and position sensor inputs are the only analog inputs on this control system.
The joystick and position sensor data can be verified by utilizing the controller. Press the
menu button until the Display Control section is selected. Then use the up/down arrows
to select either the joystick or coords for the position sensors. The menu button then must
be pressed until the default screen is again displayed. The inputs can now be viewed.
This not only guarantees that the input devices are working but that the controller is
interpreting the data. If the display indicates that the input device is not working then the
raw data can be checked. The analog inputs all range from 0 to +10 VDC. Joystick
inputs can be checked with the engine off and the controller running. The position sensor
inputs can be measured the same way however, no change can be observed. The position
sensors are calibrated and should not be changed; Therefore, the hydraulic system should
be running with the arm deployed on the opposite side of the vehicle from the controller
so that the input can be safely measured as the joints move. Position sensor inputs can be
measured from the terminal strip of the signal conditioning board located in the center of
the controller and can also be observed via the LCD display.
B.1.2 Digital Inputs
The digital inputs are used for the toggle and limit switches. The controller input is
normally high, +5 VDC, and then pulled low via a switch. For example when a switch
contact is open, the conductor coming from the controller will measure a +5 VDC
potential referenced to ground. When switched the input is pulled low, to ground, the
input is considered active.
Warning !!!
Never connect any voltage source to the digital inputs, damage to controller will occur.
Inputs are only switched to ground.
The digital inputs of the controller are normally high, nominally +5 VDC. The +5 VDC
supply is integral to the controller and pulled high via an internal pull up resistor. In this
Copyright 2011, AHMCT Research Center, UC Davis