User Guide
10-1-2013 7
• After locking the venting parts, the complete vent system
has to be fi xed to the building construction with the
supports. For vertical installation the maximum distance
between the supports is 2m (78”) and for non-vertical
installation the maximum distance between the supports
is 1m (39”). The venting system has to be sloped upwards
not less than 50mm (2”) per 1000mm (39”) from the
appliance to the connection with the vent terminal.
• Don’t install the system upside down in order to avoid
leakage of condensate.
• Making a specifi c length: when a pipe section is too long,
it’s possible to shorten this (e.g. with a hacksaw).
• Making a specifi c length: when a pipe section is too
short, it can be extended by use of an adjustable pipe.
• Remove burrs at the pipe ends.
CAUTION
Damage to the gasket can result in the
dangerous release of carbon monoxide!