User Guide

4 10-1-2013
5. CoxDENS
®
PPs system expand and contract slightly
during heating cycles. This vent system has to be
supported in accordance with these instructions.
6. Appliances can be operated immediately upon the
completion of the CoxDENS
®
PPs Vent System
installation.
7. The vent pipe of CoxDENS
®
PPs is rated to a maximum of
5000Pa (0.725psi) or 20” of water column.
8. The maximum fl ue gas temperature for CoxDENS
®
PPs is
110°C (230°F) for ULC-S636 compliant installations. Cox
Geelen guarantees CoxDENS
®
PPs up to a maximum fl ue
gas temperature of 120°C (248°F).
9. Cox Geelen Pipe lubricant (art.no. 0005CA000),
especially made for the assembly of exhaust pipes in
plumbing and heating systems. May be applied to all
gaskets for ease of assembly. Don’t use another Pipe
lubricant.
10. Free standing components (i.e., above a roof) must not
exceed a maximum vertical height of 1m (39”) (Wind
load). When the freestanding length is greater, the
ue liner has to be stabilized. The maximum distance
between the outer surface of the fl ue liner and the wall is
50mm (2”) (subjected to bracket strength).
11. The minimum clearance to combustibles materials is
zero, 0mm (0”).
12. Unless approved by the appliance manufacturer, only
one appliance may be attached to the vent system.
13. Do not use CoxDENS
®
PPs with any other manufacturer’s
vent components. Cox Geelen CoxDENS
®
PPs
components must be used exclusively throughout the
entire vent system.
- Nozzle is made of Polypropylene in the colour RAL7001,
sizes Ø60/100mm (Ø2”/4”) and Ø80/125mm (Ø3”/5);
- External air pipe of galvanised steel sheet material
without separate nozzle in the colour RAL9016, only size
Ø110/160mm (Ø4”/6”);
- Internal wall plate is made of Galvanised steel and
aluminium in the colour RAL 9016;
- Outside EPDM Wall plate is in the colour RAL7001 (grey);
Plume Management Kit:
- Termination pipes are made from UV-stabilized
Polypropylene material, only for vent system Ø60mm (2”),
Ø80mm (3”);
- Supports of PVC;
- Bird mesh made of stainless steel.
COXDENS
®
PPS COMPONENTS
For a list of ULC-S636 approved CoxDENS
®
PPs components,
please consult the CoxDENS
®
PPs catalogue at
www.coxgeelen.com.
General installation conditions
1. Do not install CoxDENS
®
PPs in areas where ambient air
temperature exceeds 150°C (302°F).
2. Do not store the CoxDENS
®
PPs system in a corrosive
environment, and keep protected from UV light (ideally in
it’s packaging).
3. The maximum continuous vertical vent length is unlimited,
the maximum distance between the supports is 2m (78”),
see fi gure 1. Always refer to the manufacturer’s instruction
for appliance specifi c vent limitations.
4. The horizontal installation length is unlimited, the
maximum distance of a non vertical installation between
the supports is 1m (39”)*, see fi gure 2. The venting system
has to be sloped upwards not less than 50mm (2”) per
1000mm (39”) from the appliance to the vent terminal,
see fi gure 3. Always refer to the manufacturer’s instruction
for appliance specifi c vent limitations.
*NOTE: To meet requirements of ULC-S636,
the maximum distance of a non vertical installation
between the brackets of the vent system 2” (Ø60mm) is
0,5m (19).