User Guide
Installation Manual Coxcentric PPs / Alu with CONNEXT
®
10-1-2013 9
Horizontal Termination
• If the position of the wall terminal is specified, make a hole
in the wall with a minimum of
• a) ∅ 105mm (∅ 4,1”) for terminal ∅ 60/100mm (∅ 2”/4”);
• b) ∅ 130mm (∅ 5,1”) for terminal ∅ 80/125mm (∅ 3”/5”);
• c) ∅ 165mm (∅ 6,5”) for terminal ∅ 110 /16 0 m m (∅ 4”/6”);
• For a good water seal, install the correct wall sealing on
the outside of the wall;
• Install the wall terminal horizontally through the wall and
fix them with the wall bracket to the inside of the wall with
4 wood screws;
• To lock the system, turn two self-drilling screws
∅ 3,5x13mm (supplied with vent) into the predrilled holes
of the wall bracket and through the metal air pipe. Don’t
use longer screws to avoid damage of the internal vent
pipe;
• The wall terminal is now ready to connect with the other
vent parts.
Terminations must be in accordance with the appliance
manufacturer’s instructions, local building code requirements,
CAN/CSA-B149.1 and CAN/CSA-B149.2.
Typical wall situation
——›
TOP VIEW