User Guide

Installation Manual Coxcentric PPs / Alu with CONNEXT
®
10-1-2013 9
Horizontal Termination
If the position of the wall terminal is specified, make a hole
in the wall with a minimum of
• a) 105mm (4,1”) for terminal 60/100mm (2”/4);
• b) 130mm (5,1”) for terminal 80/125mm (3”/5);
• c) 165mm (6,5”) for terminal 110 /16 0 m m (4”/6);
For a good water seal, install the correct wall sealing on
the outside of the wall;
Install the wall terminal horizontally through the wall and
fix them with the wall bracket to the inside of the wall with
4 wood screws;
To lock the system, turn two self-drilling screws
3,5x13mm (supplied with vent) into the predrilled holes
of the wall bracket and through the metal air pipe. Don’t
use longer screws to avoid damage of the internal vent
pipe;
The wall terminal is now ready to connect with the other
vent parts.
Terminations must be in accordance with the appliance
manufacturer’s instructions, local building code requirements,
CAN/CSA-B149.1 and CAN/CSA-B149.2.
Typical wall situation
——›
TOP VIEW