User Guide
Installation Manual Coxcentric PPs / Alu with CONNEXT
®
6 10-1-2013
INSTALLATION OF THE COXCENTRIC PPs/ALU WITH CONNEXT
®
SYSTEM
• Check the presence of the seals and their correct
placement; q
• Installation: before putting the sections together, the push
in spigot and the black seals have to be rubbed with
special Pipe Lubricant Chloride free (only obtainable at
Cox Geelen BV), so that a smooth installation is possible.
• The installation of the separate sections will be connected
by pushing the CONNEXT
®
spigot end of the section into
the socket of the previous section; w
• To lock the system, turn two self-drilling screws ∅ 3,5x13
mm (supplied with vent) into the predrilled holes of the
CONNEXT
®
spigot and through the metal air pipe. Don’t
use longer screws to avoid damage of the internal vent
pipe; e
• After locking the venting parts, the complete vent system
has to be fixed to the building construction with the
aluminum supports. For vertical installation the maximum
distance between the supports is 2 m (78”) and for
non-vertical installation the maximum distance between
the supports is 1 m (39”). The venting system has to be
sloped upwards not less than 50 mm (2”) per 1000 mm
(39”) from the appliance to the connection with the vent
terminal.
• Don’t install the system upside down in order to avoid
leakage of condensate.
• Making a specific length: when a pipe section is too long,
it’s possible to shorten this (e.g. with a hacksaw). r
• Remove burrs at the pipe ends.
• Making a specific length: when a pipe section is too
short, it can be extended by use of an adjustable pipe.
Caution
Damage to the gasket can result in the
dangerous release of carbon monoxide!
q€
w
e
€
r€